Thin Web Server                                             Connectivity Module Configuration 
 
 
7-1
 
Connectivity Module Configurator Program 
 
This utility is used to create, manage, upload, and 
dowload configuration settings to ASCO Connectivity 
Modules (only part no. 629800-xxx) that the Thin Web 
Server will be communicating with over LAN. 
 
How to Add Configuration Setting 
for a Connectivity Module (Accessory 72E) 
 
1.  Launch the Thin Web Server setup program. 
 
2. Connect to the Thin Web Server by clicking 
Communication, then Connect to Server. The indicator 
(bottom right corner) will turn from red to green. 
 
3.  On menu bar click Utilities then _72E List Editor
 
4.  The _72E Device List Editor screen displays. 
 
5.  Click the Add Device button.  
 
6. 
Set the IP Address, the type of Controller, Power Manager, 
and the address of the devices here. Note that there is only 
one item pertaining to the device address. This means that 
both devices must be set with the same address when 
connected to the Connectivity Module.
 
 
NOTE: Only for ATSs with Group 1 Controller (Series 
300) and Group 6A/7A Control Panels (ASCO 940, 962, 
436, 434, 447, 448) can you specify their name and 
location from here. ATSs with Group 5 Controller (4000 
Series, 7000 Series) are done either on their controller or at 
the Thin Web Server detail page. 
 
7.  Click the Save record button to save your setting or 
Cancel if you want to discard the changes you made. 
 
continued on next page 
 
Click the 
Add Device 
button. 
Click the 
Save record 
button.