The Heat Pump air conditioning system shall be an EMI AmericaSeries split system. The system shall consist of a 
Floor mounted packaged evaporator section Model FHP12 and matching AmericaSeries outdoor unit Model SHC09. 
The units shall be made within North America. The units shall be listed by Intertek Testing Service (ITS) and bear 
the ETL label. All wiring shall be in accordance with the National Electrical Code (N.E.C.). The units shall be rated in 
accordance with ARI Standard 210/240 and bear the ARI label. The units  shall  be manufactured in a facility certifi ed 
to ISO 9001, which is an international standard used to provide guidance in the development and implementation 
of an effective Quality Management System. The condensing unit shall contain an R-22 refrigerant charge for the 
evaporator section and condenser section. System SEER shall meet or exceed 1992 Federal Standards.
 PART TWO “WARRANTY”
The units shall have a manufacturer’s warranty for a period of one (1) year from date of installation. The compressor 
shall have a warranty of fi ve (5) years from date of installation. If, during this period, any part should fail to function 
properly due to defects in workmanship or material, it shall be replaced or repaired at the discretion of Enviromaster 
International LLC. This warranty does not include labor. Manufacturer shall have fi fteen years experience in the U.S. 
market.
 PART THREE “PERFORMANCE”
Each indoor unit shall provide a total minimum cooling capacity of 9,500 Btuh with an SEER of 10.5 and EER of 10.0 
at ARI standard conditions. The system net minimum total cooling capacity shall be 9,500 Btuh and the net minimum 
sensible cooling capacity shall be 7,050 Btuh with a circulating air rate of 440 CFM at 80
o
 F (DB)/67
o
 F (WB) entering 
the indoor coil and 95
o
 F (DB) air entering the outdoor coil. The total power consumption of the combined system 
shall not exceed 950 Watts at these conditions.
HEATING
The system shall provide a heating capacity of 9,000 Btuh with a HSPF of 7.1 at ARI standard conditions.  
The heating capacity at 70º F indoor and17º F outdoor shall be 5,300 Btuh.  
 PART FOUR “INDOOR UNIT”
The  indoor  unit  shall  be  factory  assembled,  wired  and  contain  a  low  voltage  transformer. The  cabinet  shall  be 
fabricated of G60 galvannealed steel, fi nished in “off-white” with corrosion inhibiting polyester powder-coated paint.  
The evaporator fans shall be a forward curve centrifugal type, dynamically balanced and directly mounted to the 
motor shafts.  The motor shall be PSC type with internal thermal overload protection.  Return air shall be fi ltered by 
means of an easily removable electrostatic washable fi lter. The indoor unit shall have fresh air capability through the 
back of the unit. The evaporator coil shall be of nonferrous construction with louvered fi ns bonded to rifl ed copper 
tubing. The tubing shall have inner grooves for high effi ciency heat exchange. All tube joints shall be brazed with 
phoscopper or silver alloy. The coil shall be pressure tested at the factory. A condensate pan and drain shall be 
provided under the coil. System refrigerant fl ow shall be controlled by means of an orifi ce piston in the indoor unit. 
The unit electrical power shall be 208/230 Volts, 1 phase, 60 Hertz. The system shall be capable of satisfactory 
operation within voltage limits of 208/230 +/- 10% Volts.
 PART FIVE “CONTROL SYSTEM”
The control system shall consist of unit-mounted infrared compatible controls. Interconnect low-voltage 
W
iring shall 
run from indoor unit to outdoor unit direct. 
NO SPLICES. When running low voltage wiring a double insulated, 5-wire 
18 gage cable is mandatory or use shielded 5-wire cable. The microprocessor shall be factory wired and located 
within the indoor unit. It shall have the capability of sensing return air temperature and indoor coil temperature; large 
¾” LCD backlit display; operational range adjustable between 55º F and 95º F in one-degree increments; anti-short 
cycle compressor protection; minimum compressor run time; fan purge, fan remains on for 60 seconds after heat/cool 
call is dropped for improved effi ciency; freeze protection to prevent evaporator freeze ups; annunciation provides an 
audio feedback when the control settings are changed; universal control board allows the unit to operate with either 
a straight cool or heat pump condenser; two stage heating when optional electric heat and heat pump condenser 
EMI ENGINEERING SUBMITTAL DFPH093 (FHP12-SHC09)