Efficient Networks Siemens Sinamics S120 User Manual

Page of 560
Applications 
 
11.3 Motor changeover 
 
Drive Functions 
458
 
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4 
U
U
U
S>@
.+
.
.
.
.
8
9
:
8
9
:
.
.
.
.
.+
.+
.+
S>@
 
Figure 11-3  Example: star/delta switchover 
Table 11-4  Settings for the example 
Parameter 
Settings 
Comments 
p0130 
Configure 2 MDS. 
p0180 
Configure 2 DDS. 
p0186[0..1] 
0, 1 
The MDS are assigned to the DDS. 
p0820 
p2197.2 
p0821 to p0824 0 
Switchover to delta connection after speed in 
p2155 is exceeded. 
p0826[0..1] 
0; 0 
Identical numbers signify the same thermal 
model. 
p0827[0..1] 
1, 2 
Assign the bit from p0830 to the MDS. If  
p0827[0] = 1, for example, bit p0830.1 is set when 
MDS0 is selected via DDS0. 
p0830.1 and p0830.2 
Digital outputs auxiliary 
contactors 
The digital outputs for the auxiliary contactors are 
assigned to the bits. 
p0831[0..1] 
Digital inputs auxiliary 
contacts 
The digital inputs for the checkback from the 
motor contactors are assigned. 
p0833.0..2 
0, 0, 0 
The drive is responsible for controlling the 
contactor circuit and the pulse inhibit. Parking bit 
(Gn_ZSW14) is set. 
p2155 
Switchover speed 
Sets the speed at which the switchover is to be 
carried out in delta. 
Procedure for star/delta switchover 
1.  Start condition: 
For synchronous motors, the actual speed must be lower than the star field weakening 
speed. This prevents the regenerative voltage from exceeding the terminal voltage. 
2.  Pulse inhibit: 
After selecting a new drive data set using p0820, the pulses are inhibited.