Cyclades PM IPDU User Manual

Page of 102
46
        Cyclades PM IPDU Installer/Administrator/User Guide
To display the ID of PM IPDU 2, enter the following.
To rename an ID to “sammy,” using an existing ID “QA,” enter the following.
To display the IDs of all PM IPDUs in the daisy chain, enter the following.
interval
The interval command configures the power up interval for each outlet in the system. The power up 
interval of an outlet is the time (in seconds) the unit will wait, after turning this outlet on, to turn on 
any other outlet. This command is available to the admin user only.
Syntax 
interval <outlet_number> <duration>
Arguments
<duration>
 
Sets the power up interval of outlets. Valid intervals are from 0 to 100. Default 
value is 0.5
NOTE: When this value is set to 0.0, there is still a power up interval of approximately 0.1 seconds 
between outlets.
<outlet_number>
 
Outlet number, such as “5”, outlet name such as “sunfire”, or group of 
outlets such as “1, 3-5”
Examples
To display the interval of outlet 1, enter the following.
pm>id 2
IPDU #2: id = QA
pm>id QA sammy
IPDU #2 = sammy
pm>id
IPDU #1: id = R&D
IPDU #2: id = QA
pm>interval 1
1: Outlet power on interval is 0.0 sec.