CyberPower CS150U48V3 User Manual

Page of 18
© 2010 CyberPower Systems (USA), Inc. All Trademarks are property of their owners.
Page:  11 of 17
4.7 Connecting to Power Source
4.7.1 Installing the Power Cord 
1. Remove the 4 terminal strip cover screws 
(upper left hand corner)
2. Remove any convenient 3/4” knock-out of 
the UPS enclosure.
3. Install a Heyco Liquid Tight Cordgrip 
    (LTF-11) or equivalent, if not using conduit.
4. With the power cord disconnected from any 
supply source, route the power cord 
through the strain relief and attach it to the 
terminal strip.
5. Tighten the strain relief around the power 
cord to secure.
6. Re-install the terminal strip cover.
7. Plug-in the molded power plug on the front 
of the UPS control panel. 
Note: Be certain to utilize environmentally 
sealed strain-reliefs, cordgrips, or conduit at 
the AC Power entry point.
Note: Be sure to connect the power cord to 
each terminal (L/N/G) correctly and securely. 
Figure 14: AC Wiring (i)
Figure 15: AC Wiring (ii)
Remove 
terminal cover
Remove 
knock-out and 
add strain relief 
or conduit here
4.6 Battery Heater - BTH-150-8X (Optional)
Figure 12: Block Diagram of Battery Heater
Table 1: Battery Heater Specifications
Table 2: Block Diagram Descriptions
Figure 13: Battery Heater Dimensions
DESCRIPTION:
DIMENSIONS:
Input Voltage 
    (AC) 110V/60Hz
Wattage 
    120W
Line Cord Thermostat 
    OPEN
:15˚C     CLOSE:5˚C
Thermal Fuse 
    84˚C
Mat Mounted Thermostat     OPEN
:50˚C     CLOSE:35˚C
3
4
1
2
3
4
Heater
Location          Device 
                 Function
        Power Connector          AC Input
        Line Cord Thermostat     In low temperature conditions the thermostat    
 
                                                will allow power to flow to the heater mat coil
        Thermal Fuse 
        Final protection allows safe failure
        Mat Mounted                   The thermostat is to keep the temperature of
  
        Thermostat                   the battery heater within a pre-set range.
296
65
8
20
4
280
4-Ø10
28.55
115.5
37.55
28
16
Thermal Switch & Thermal Fuse
On Back
Heater Area
260
12
2-Ø4
Note: Make sure that the input voltage for the battery heater 
is 110V.