Trouble Shooting (Cont’d)


Following normal 
operation, dome 
will rotate one 
revolution while 
being controlled 
The system could not verify the 
start position and initiates a self 
calibration.   
This is a normal self calibration event. 
No action required. 
If this happens frequently, 
verify the tab alignment 
with the photoelectric 
switch 
    8 
Vertical range is not 
within 90

2 degree 
with large deviation 
Fault occurs when the dome 
device is in tilt movement. It may 
be caused by obstruction of 
camera which leads to early tilt 
movement 
Check and adjust the mechanical   
installation and remove any 
obstructions from the camera vertical 
platform. 
 
Wrong communication settings 
Set the correct protocol, baud rate and 
address of dome device 
Self-test is normal, 
but cannot control 
dome 
Improper connection of control 
cable (polarity) 
Verify the polarity of the RS485 
connection as per the instruction 
manual 
Follow installation 
instructions 
Maximum Communication cable 
run is exceeded   
Add amplification circuit for RS485 
Intermittent or incorrect 
connections 
Verify the wiring 
Slip ring is damaged 
Replace the slip ring 
10 
Intermittent control 
of dome device 
RS-485 protective discharge 
arresters are damaged 
Replace RS485 protective discharge   
arresters (qualified service only) 
This situation may occur 
following intense electric 
storms or severe lightning.   
11 
Call out function 
fails 
System failure caused by noise 
interference 
Restart the dome device 
 
12 
Dome operates by 
itself occasionally 
No transmission auto “call back” 
function is set to the dome device 
Verify this setting 
 
13 
One dome works 
well while other do 
not under identical 
operation 
Incorrect communication settings 
or wiring 
Verify the communication setting and 
wiring again 
Follow installation 
instructions