Fujitsu DX60S2 User Manual
Chapter 1 Hardware Configurations
1.5 Power Distribution Units (Only for Regions Other than EMEA&I)
1.5 Power Distribution Units (Only for Regions Other than EMEA&I)
ETERNUS DX60 S2 Disk storage system User’s Guide -Site Planning-
23
Copyright 2012 FUJITSU LIMITED
P3AM-5492-04ENZ0
1.5
Power Distribution Units (Only for Regions Other than
EMEA&I)
EMEA&I)
There are two sizes for power distribution units: 1U and 2U.
A power distribution unit is an option to connect power supply units to power outlets when power
sockets are limited.
A power distribution unit is an option to connect power supply units to power outlets when power
sockets are limited.
■
Power distribution unit for DX60 S2 (AC200-240V, 1U, Max 2 enclosures connection)
There are four outlets and two inlets.
Figure 1.26 Power distribution unit (AC200-240V, 1U, Max 2 enclosures connection)
The following table shows the specifications of a power distribution unit and the AC cables that
are provided.
are provided.
Table 1.8
Power distribution unit (AC200-240V, 1U, Max 2 enclosures connection) and
provided AC cable specifications
Item
Specifications
Power
Voltage
AC200 - 240V
Phase
Single
Frequency
50Hz/60Hz
Input cable
Connection type
IEC60320-C13
↔ NEMA L6-15P
Length
4m
Quantity
2
Output cable
Connection type
IEC60320-C13
↔ IEC60320-C14
Length
3m
Quantity
4
Outlets (OUTPUT)
Inlets (INPUT)