Chapter 3  Connections
  3.4  Power Synchronized Connections
ETERNUS DX60 S2 Disk storage system User’s Guide -Site Planning-
50
Copyright 2012 FUJITSU LIMITED
P3AM-5492-04ENZ0
When connecting one or two servers
Figure 3.11 Power control using a power synchronized unit (when connecting one or two 
servers)
Powering on sequence
1
Power on of all the server UPS units
2
Server startup
The server OS startup is suspended until the ETERNUS DX Disk storage system 
startup is complete (*1).
3
Issuance of command to turn on the ETERNUS DX Disk storage system from the 
power synchronized unit
4
ETERNUS DX Disk storage system startup
*1:
The server must be set to suspend server OS startup until the ETERNUS DX Disk storage 
system startup is complete.
Powering off sequence
1
Shutdown of all the servers
2
Shutdown of all the server UPS units
3
Issuance of command to turn off the ETERNUS DX Disk storage system from the 
power synchronized unit
4
ETERNUS DX Disk storage system shutdown
RS232C cable
Server
ETERNUS DX
 Disk storage system
PWC
UPS setting
Power synchronized unit
PWC
UPS
UPS 
management 
software
An instruction is 
issued to turn on/off 
the ETERNUS DX 
Disk storage 
system when AC 
output/no AC output 
is detected.
Turns on: 1
Turns off: 2
3
4
Turns on: 2
Turns off: 1