Artesian Spas Hot Tub Grand Bahama User Manual

Page of 88
56
Topside Controller Instructions cont...
Temp/Set (80°F - 104°F / 26°C - 40°C)/ Freeze 
Protection
Temp/Set (80°F - 104°F / 26°C - 40°C)
The start-up temperature is set to 100°F/37°C.  The Last measures 
temperature is constantly displayed on the LCD.  
NOTE:  The last measured spa temperature displayed is current 
only when the pump has been running for at least 1 minute.
To  display  the  set  temperature,  press  the  “Cool”  or  “Warm”  pad 
once.  
To change the set temperature, press the pad a second time before 
the LCD stops flashing.  Each press of the “Cool” or “Warm” pad will 
continue to either lower of raise the set temperature respectively.  
After three seconds, the LCD will stop flashing and display the cur-
rent spa temperature.   
Freeze Protection
If the temperature sensors detect a drop to below 44°F/6.7°C within 
the heater, the pump will automatically activate to provide freeze 
protection.  The equipment stays on until 4 minutes after the sen-
sors  detect  that  the  spa  temperature  has  risen  to  45°F/7.2°C  or 
higher.  In cold climates, an additional freeze sensor may be added 
to protect against freeze conditions that may not be sensed by the 
standard sensors.  Aux freeze sensor protection acts similiarly ex-
cept with the temperature thresholds determined by the switch and 
without a 4-minute delay in turnoff.  See your dealer for details.