American Standard CH530 User Manual

Page of 116
93
CDHF-SVU01C-EN
 WARNING
Hazardous Voltage
w/Capacitors!
Disconnect all electric power,
including remote disconnects before
servicing. Follow proper lockout/
tagout procedures to ensure the
power cannot be inadvertently
energized. For variable frequency
drives or other energy storing
components provided by Trane or
others, refer to the appropriate
manufacturer’s literature for
allowable waiting periods for
discharge of capacitors. Verify with
an appropriate voltmeter that all
capacitors have discharged. Failure
to disconnect power and discharge
capacitors before servicing could
result in death or serious injury.
Note: For additional information
regarding the safe discharge of
capacitors, see PROD-SVB06A-EN or
PROD-SVB06A-FR
Normal Chiller Operating Characteristics
Operating Characteristic
Normal Reading
Approx. Evaporator Pressure
6 to 9 PSIA (-9 to -6 PSIG)
Approx. Condenser Pressure
17 TO 27 PSIA (2 to 12 PSIG)
(See Notes 1 and 2)
(Standard Condensers)
Oil Sump Temperature:
Unit Not Running
140°F to 145°F
(60°C to 63°C)
Unit Running
80°F to 162°F
(26.6°C to 72°C)
Differential Oil Pressure
18 to 22 psid
Periodic
Maintenance
Weekly Maintenance
[ ] Complete all recommended daily
maintenance procedures and checks.
Complete logs on a daily basis.
Every 3 Months
[ ] Complete all recommended
weekly maintenance procedures.
Refer to the previous sections for
details.
[ ] Clean all water strainers in the
CenTraVac water piping system.
Every 6 Months