Adtran Recording Equipment 850 User Manual

Page of 10
4
Issue 2, June 2000
61200376L1-5B
Table 1. TA 850 Backplane Connections
UL 1950 Deployment Guidelines.
One of the follow-
ing two powering schemes shall be used when power-
ing this equipment:
1. Use the ADTRAN power supply (part number
1175043L1).
2. Do the following:
a. Connect the unit to a reliably grounded -48 Vdc
source which is electrically isolated from the AC
source.
b.A readily accessible disconnect device, suitably
approved and rated, shall be incorporated in the
input source wiring.
c. The branch circuit overcurrent protection shall be a
fuse or circuit breaker rated minimum 48 V, maxi-
mum 20 A.
d.This unit shall be installed in accordance with the
requirements of NEC NFPA 70.
The installation configurations codes are given below:
Alternate Connections.
For wire-wrap or screw
terminal connections, the rear cover does not need to be
removed; only the terminal access cover needs to be
removed. Make wire-wrap or screw terminal
connections as follows:
1. Unscrew the access cover hold-down screw.
2. Slide the access cover down slightly to disengage the
lock-tabs from their slots.
3. Identify the wire-wrap pins designated for use, and
make the connections starting with the pins closest to
the exit port to avoid wiring interference as work
progresses.
4. If alternate power connection to P7 is to be used,
make those terminal connections last.
5. Carefully route wiring through the exit port.
6. Position and align the access cover tabs to the slots;
insert the tabs and slide the cover up slightly until
the screw holes are aligned. Ensure that exit wiring is
not pinched or damaged.
7. Reinsert the hold-down screw.
Customer Connection.
One 50-pin male amphenol
connector (P2) provides the interconnect wiring for the
access modules located in slots 1 through 6 of the chas-
sis. This connector is usually terminated with a punch-
down block for premises wiring or connected directly
to a cross-connect or main distribution frame. Figure 4
on page 5 details the connector pinout.
T1 Connection.
There are two termination points for
connecting the network T1 to the chassis: the primary
RJ-48 connector (JP2) and the alternate wire-wrap pins
on terminal strip P3 (as shown in Figure 2 on page 2).
Only one connector type is used (not both).
The T1 primary connection is via the RJ-48 connector labeled
T1 (JP2). This arrangement provides a convenient T1 connec-
tion for those installations where a T1 Smart Jack is used.
The RCU common module provides termination for
DSX-1 and DS1 signals. For wire-wrap connections, shield
is provided by the ground pin adjacent to the DSX-1/DS1
pin set (see Figure 5 on page 5). Line build-out and equal-
ization settings are provisioned on the RCU.
Power Connection.
There are two power connec-
tions on the backplane: a modular DC plug (P6), and a
three lug terminal strip (P7). (Refer to Figure 2 on page 2.)
The primary connection is the modular plug, which
receives -48 VDC from the ADTRAN power supply/
battery charging unit (P/N 1175043L1). The alternate
Ref Des
Device/Label
Technology
P1
wire-wrap strip
clock/tests
P2
50 pin amphenol
FXO, FXS, etc.
P3
wire-wrap strip
alternate T1 interface
P5
wire-wrap strip
alarms
P6
4 pin jack
primary -48 V in
P7
3-lug terminal
alternate -48 V in
JP1
RJ-48/E-NET
10BaseT Ethernet
JP2
RJ-48/T1
primary T1 interface
JP3
RJ-48/FT1
DSX1 interface
JP4
RJ-48/MAINT
RS 232 craft interface
J1
V.35
Nx56K/64K
In
Out
PC
F
C
IC
E
-
TC
X
X
CAUTION
Both Power and T1 services have two connection
points. In all cases, only one of the connection
points is used. Adhere to the instructions in the
following subsections to ensure correct installation.
CAUTION
Use wire gauge suitable for the application.