DMP Electronics XR2500F User Manual

Page of 60
XR2500F Installation Guide 
Digital Monitoring Products
17
InstallatIon
11.7  XR2500F Standby Battery Calculations
Standby Battery Power Calculations
Standby Current
Alarm Current
XR2500F Control Panel 
Relay Outputs 1-2 (ON) 
Switch Grounds 3-6 (ON) 
Active Zones 1-8 
Active Zones 9-10 
2-Wire Smoke Detectors 
Panel Bell Output
Qty ___  1_
Qty ______
Qty ______
Qty ______
Qty ______
Qty ______
x
x
x
x
x
x
180mA
30mA
5mA
1.6mA
4mA
0.1mA
__180_mA
______
______
______
______
______
Qty ____1_
Qty ______
Qty ______
Qty ______
Qty ______
Qty ______
x
x
x
x
x
x
180mA
30mA
5mA
*2mA
30mA
0.1mA
1500mA
__180_mA
______
______
______
______
______
______mA
893A Dual Phone Line Module
Qty ______
x
12mA ______
Qty ______
x
50mA ______
461 Interface Adaptor Card
7mA ______
x
7mA ______
462N Network Interface Card
Qty ______
x
50mA ______
Qty ______
x
50mA ______
462P Printer Interface Card
Qty ______
x
50mA ______
Qty ______
x
50mA ______
463G Digital Cellular Communicator Card
Qty _______
x
21mA ______
Qty _______
x
21mA ______
481 Expansion Interface Card
Qty ______
x
15mA ______
Qty ______
x
15mA ______
860 Relay Output Module (one relay active) 
All four relays active
Qty _______
x
34mA
138mA
______
______
Qty _______ 
x
34mA
138mA
______
______
865 Style Y or Z Notification Module
Qty ______
x
26mA ______
Qty ______
x
85mA ______
866 Style W Notification Module
Qty ______
x
45mA ______
Qty ______
x
76mA ______
867 LX-Bus Style W Notification Module
Qty ______
x
30mA ______
Qty ______
x
86mA ______
630F Remote Fire Command Center
Qty ______
x
63mA ______
Qty ______
x
92mA ______
690 Security Command Keypad
Qty ______
x
77mA ______
Qty ______
x
84mA ______
693/793 Security Command Keypad 
Active Zones (EOL Installed)
Qty ______
x
92mA
1.6mA
______
______
Qty ______
Qty ______
x
x
120mA
*2mA
______
______
790 Security Command Keypad 
Active Zones (EOL Installed)
Qty ______
x
77mA
1.6mA
______
______
Qty ______
Qty ______
x
x
84mA
*2mA
______
______
7060/7060A/7160 Thinline Keypad
Qty ______
x
80mA ______
Qty ______
x
84mA ______
7063/7063A/7163 Thinline Keypad
Qty ______
x
86mA ______
Qty ______
x
112mA ______
7070/7070A/7170 Thinline Keypad 
Active Zones (EOL Installed)
Qty ______
x
72mA
1.6mA
______
______
Qty ______
Qty ______
x
x
87mA
*2mA
______
______
7073/7073A/7173 Thinline Keypad 
Active Zones (EOL Installed)
Qty ______
x
93mA
1.6mA
______
______
Qty ______
Qty ______
x
x
112mA
*2mA
______
______
733 Wiegand Interface Module 
Active Zones (EOL Installed) 
Annunciator (ON)
Qty ______
Qty ______
x
x
30mA
1.6mA
______
______
Qty ______
Qty ______
Qty ______
x
x
x
30mA
*2mA
20mA
______
______
______
734 Wiegand Interface Module 
Active Zones (EOL Installed) 
Annunciator (ON)
Qty ______
Qty ______
x
x
30mA
1.6mA
______
______
Qty ______
Qty ______
Qty ______
x
x
x
30mA
*2mA
20mA
______
______
______
Copy Sub-Totals to next page
 
Sub-Total Standby
*Based on 10% of active zones in alarm.
______mA
Sub-Total Alarm ______mA