DMP Electronics XR2500F User Manual

Page of 60
XR2500F Installation Guide 
Digital Monitoring Products
29
InstallatIon
Area Information
26.1  Ownership
The control unit system shall be under one ownership.
26.2  Annunciation
The System shall be installed so that when arming any area from any keypad, the local bell shall annunciate.
26.3  Trouble Display
The Status List programming shall be set to annunciate all trouble messages at all keypads.
26.4  Closing Wait
The Closing Wait option must be programmed YES.
26.5  Local Bell Supervision
When a local bell is employed, the power supply for the bell shall be under 24-hour protection. Proper
personnel for maintenance or security of the system shall be able to disarm that area.
Household Burglar-Alarm System Units 
ANSI/UL 1023
27.1  Audible Devices
At least one listed audible device (Ademco AB12M) rated to operate over the voltage rate of 11.7 VDC to
12.8 VDC and rated at 85 DB minimum must be used.
27.2  Auxiliary Circuits
At least one burglary alarm initiating device shall be used on the system. If the voltage for the device is
applied by the control unit the burglary alarm initiating device shall be rated to operate over the range of
11.5 VDC to 12.7 VDC.
27.3  Bell Cutoff
The Bell Cutoff time cannot be less than five minutes.
27.4  Entry Delay
The maximum entry delay used must not be more than 45 seconds. 
27.5  Exit Delay
The maximum exit delay used must not be more than 60 seconds.
27.6  Weekly Test
The product should be tested weekly.
27.7  Wireless Audible Annunciation Option
The Wireless Audible option must be selected as DAY for residential applications.
Central-Station and Proprietary Burglar-Alarm Units 
ANSI/ UL 1610 AND ANSI/UL 1076
28.1  Opening/Closing Reports
The Opening/Closing Reports option must be programmed as YES. .
28.2  Closing Wait
The Closing Wait option must be programmed YES.
28.3  Entry Delay
The maximum entry delay used must not be more than 60 seconds.
28.4  Exit Delay
The maximum exit delay used must not be more than 60 seconds.