DMP Electronics Inc. Smoke Alarm P83848 User Manual

Page of 7
Sheet 1 of 7
,167$//$7,21#3;6;7;
;56#$8',%/(#+251#6752%(
Thank you for using our products.
INSTALLATION INSTRUCTIONS
AUDIBLE HORN STROBE TWO WIRE APPLIANCES
(WALL MOUNT VERSIONS)
Use this product according to this instruction manual.  Please keep this instruction manual for future reference.
GENERAL:
DMP’s Audible Horn Strobe Appliances require only 2-wires for operation of the horn and strobe appliance and provide a selectable
continuous or Code 3 Horn tone and continuous strobe when connected directly to the Fire Alarm Control Panel (FACP).  They can
also provide a synchronized Code 3 horn tone and synchronized strobe when used in conjunction with a Sync Module (831) or Dual
Sync Module (832).  They are the ideal choice for applications where the audible silence feature is required.  The Audible Horn Strobe
Appliances are UL Listed under Standard 1971 for Signaling Devices for the Hearing Impaired and UL Standard 464 for Audible
Signal Appliances.  The 15 candela wall mounted strobes are listed at 15 candela under UL Standard 1971 and meet 75 candela
intensity on axis with low current draw.  They are listed for indoor use only and equipped with a Horn Strobe Mounting Plate (823)
that can be mounted to single-gang, double-gang, 4” backbox, 100mm European backbox or SHBB surface backbox (See Mounting
Options).  These strobe models are Listed for wall mounting only.  The Audible Horn Strobe Appliances use a Xenon flashtube with
solid state circuitry enclosed in a rugged Lexan
 lens to provide maximum visibility and reliability for effective visible signaling.
Audible Horn Strobe Appliances can be field set for High (HI) or Low (LO) dBA sound output.
These strobe models are designed for use with either filtered DC (VDC) or unfiltered Full-Wave-Rectified (VRMS) input voltage.  All
inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a FACP.
NOTE:  All CAUTIONS and WARNINGS are identified by the symbol 
.  All warnings are printed in bold capital letters
WARNING:  PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT.  FAILURE
TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN
IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY
SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU
AND/OR OTHERS.
SPECIFICATIONS:
Table 1:  UL Ratings
Models
Nominal
Rated
Strobe
Voltage
Voltage Range
Candela
(VDC/VRMS)
(VDC/VRMS)
(cd)
803
12
10.5-15.6
15*
* 15cd models are UL Listed for 15cd and meet 75cd on axis.
Table 2A:  dBA Sound Output
Description
Volume
Reverberant Per UL 464
Anechoic dBA
10.5VDC
12.0VDC
15.6VDC
10.5VDC
12.0VDC
15.6VDC
Low
73*
76
76
82
84
86
Continuous Horn
High
82
82
85
87
89
91
Low
67*
70*
70*
82
84
86
Code 3 Horn
High
76
76
79
87
89
91
2841 E. Industrial Drive, Springfield, MO  65802-6310  800-641-4282
WARNING:  AUDIBLE HORN STROBE APPLIANCES SET ON LOW dBA DO NOT MEET THE 75dBA MINIMUM
UL REVERBERANT SOUND LEVEL REQUIRED FOR PUBLIC MODE FIRE PROTECTION SERVICE (NOTED BY *