Delta DELTA DUP-B User Manual

Page of 491
 
Chapter 3 Creating and Editing Screens 
Revision May, 2010 
 
 
3-101 
Property Description of Multistate Buttons 
Set Low Security 
Use this option to force the current priority to be the lowest after 
the button is pressed. This can prevent the misoperation made by 
the user (operator).   
InterLock Address 
InterLock Level 
When InterLock Address is set to be ON or OFF (this is determined 
by the property of “InterLock Level”), this button can be enabled.   
Before Execute 
Macro 
If this option is set, when the user presses the button, the system 
will execute the command of this macro first and then perform the 
operation of this button. But, if the state of the button is not 
triggered by pressing the button (via macro or external signal), the 
command of this macro will not be executed. 
After Execute 
Macro 
If this option is set, when the user presses the button, the system 
will perform the operation of this button first and then execute the 
command of this macro. But, if the state of the button is not 
triggered by pressing the button (via macro or external signal), the 
command of this macro will not be executed. 
Enable the   
confirm window 
When this option is set, an Action Confirm dialog box will appear 
to prompt the user everytime when the button is pressed.   
Invisible Address  When this option is set to On, this button element will be invisible. 
Used to set X coordinate 
Used to set Y coordinate 
Width 
Used to set the element width 
Height 
Used to set the element height 
 
Example of Multistate Buttons:   
When the data length is LSB (D100.0 ~ D100.3): 
 
 
 
 
 
S0=D100.0 ON 
S1=D100.1 ON 
S2=D100.2 ON 
S3=D100.3 ON