Atlantis Land A03-OP3000-RC OnPower 3000 A03-OP3000RC User Manual

Product codes
A03-OP3000RC
Page of 3
ATLANTIS LAND S.p.A. Viale De Gasperi, 122 - 20017 Mazzo di Rho (MI)
Tel. 02 9390.6085 - Fax 02 9390.6161 - www.atlantis-land.com - info@atlantis-land.com
PRODOTTO: On Power Sinewave UPS 1000VA
CODICE: A03-HP1001
CODICE EAN: 8026974006239
PRODOTTO: Host Power Sinewave Line Interactive UPS 1500VA
CODICE: A03-HP1501
CODICE EAN: 80269740062346
MODEL
Power Rating
Power Rating
INPUT
OUTPUT
BATTERY
PROTECTION
ALARMS
DISPLAY
PHYSICAL
VOLTAGE(Vac)
Frequency(Hz)
Phase
Input Power Factor
Voltage(Vac)
Rated Power Factor
Load Power Factor
Wave Form
Voltage Regulation
Transient Reponse (ms)
Frequency Stability
Synchronization
Transfer Time
Crest Factor
Efficiency (AC to AC)
Run Time (Full Load)
DC Start
Input Power Factor
Type
Quantity(pcs)
Voltage(Vdc)
Recharge Time
Supplem. Charger
Short Circuit
OverHeat
High Voltage Trip
Battery Low
Noise Suppression
Spike Suppression
Audible and Visual
Self Diagnostics
LED
Dim (W*H*D) mm
Outlets
Net Weights (Kgs)
OverLoad
A03-OP1000-RC
A03-OP3000-RC
160-280
50
5%(Auto Sensing)
±
Single
>0.98(Full Load)
220/230/240
0.7 Lagging
0.5 Lagging to Unity within KW rating of unit
Sine Wave, THD<3%(no load to full load)
±
2%
±
4% under Full Load, change and corrected within 60ms
±
0.5Hz (Free Running)
Slew Rate:1Hz/Sec. Max. Synchronizing Window
5%
±
0ms
3:1
>88%
>8min.
3
36
443*88*385
3*IEC
1*Schuko
Terminal
2*Schuko
443*176*482
8
96
Yes
>0.98(Full Load)
Maintenance Free Sealed Lead Acid
8 Hours to 90%
Optional 200W/500W Chargers for extended backup application
Hold Whole System
Switch to Bypass
Switch to Backup Mode
Alarm and Switch Off
Complies with EN50091-2
Complies with EN610000-4-5
Line Failure, Battery Low, Tranfer to Bypass, System Fault Conditions
Push Button (On Demand)
Utility, Battery, Inverter, Bypass, Self-Test, OverLoad, Load/Battery Level and Fault
AC Mode:
1) <105% continuously
2) 105%-120% delay 60 seconds before switching to bypass
3) 120%-150% delay 10 seconds before switching to bypass
4) >150% immediately  switching to bypass
Backup Mode: Same Delay Time as AC Mode, then completely shutdown
700 W
2100 W
1000 VA
3000 VA
16
39
Company Certified ISO 9001:2000