Eaton 8NM1U. Switched PDU 68130 Leaflet

Product codes
68130
Page of 2
Technical characteristics
Ampmeter PDU, Switched PDU
Headquarters
140, avenue Jean-Kuntzmann
ZIRST - Montbonnot Saint-Martin
38334 Saint-Ismier Cedex - France
Tel.: +33 (0)4 76 18 30 00
IPDU486UK-04/05
Due to developments in technical standards and the equipment described in this document, we cannot be held liable for complianc
e with the characteristics indicated by the images and text unless they are confirmed by us. All the brand names referred to in
this document are protected by copyright.
Publication: MGE UPS SYSTEMS (April 2005) - Design and rewriting: 3c-evolution.com - Integration: Pamplemousse: +33 4 79 37 87 
66 – Translation: TTP: +33 4 78 66 47 99.
MGE Sensor for PDU / 68 170
Switched PDU 8 redundant 1U / 68 132
Switched PDU 16 V redundant / 68 136
Main features
Temperature/humidity supervision,
slave expansion module for 8 NM: synchronous slave expansion module for 16 V NM: synchronous
alarm threshold settings
remote reboot and power on/off commands
remote reboot and power on/off commands
for dual cord servers - expansion of the Switched for dual cord servers - expansion of the Switched
PDU 8 NM functions from 8 to 16 outlets
PDU 16 NM functions from 16 to 32 outlets
Input / output
Port 
connection to 2 RJ 11ports of the PDU
RS 232 Link port on front face for connection to NM master models
(H x W x D) in mm, weight in kg
3050 x 10 / 0.1 kg
44 x 437 x 177 mm / 3 kg
1156 x 44 x 57 mm / 3.4 kg
Switched PDU
8 NM 1U / 68 130
16 V NM / 68 134
Outlet remote management via in-band 
remote supervision via modem or Ethernet port 
and out of band supervision, power-up 
(Telnet/HTML/SSH/SNMP)
sequencing, dynamic current measurement 
digital display dedicated to current measurement for local supervision
of the connected equipment
Input current alarm threshold
remote setting and local setting through RJ 45 port
Temperature/Humidity supervision
MGE sensor for PDU (option)
Input / output
Voltage, frequency input & output, input current rating
230 V (Ph+N), 50/60 Hz, 16 Amp
Inlet type
1 x IEC 320 C 20 16 A male inlet (2 m cord  IEC 320 C 19 female/FR-Schuko male supplied). Inlet cable locking system supplied
Outlet type
8 x IEC 320 C 13, 1 LED per outlet for local status 
16 x IEC 320 C13, 1 LED per outlet for local status supervision, 
supervision, cable locking system
cable locking system 
Maximum current rating per outlet/per outlet group
10 A / 16 A max per each 8-outlet group
Dimensions / Weight
Mounting mode 
horizontal rack mounting (1U), 2 mounting brackets
vertical rack mounting, 2 removable flanges supplied with brackets
(H x W x D) in mm / weight in kg
44 x 437 x 177 mm / 3 kg
1156 x 44 x 57 mm / 3.4 kg
Ampmeter PDU 
12 V / 68 141
12 NM 2U / 68 152
Dynamic current measurement 
digital display for local supervision
local (1 display per 2-outlet group) and remote supervision 
through Web browser or modem
Alarm threshold setting for input current
local setting through RJ 45 port and remote setting via Webbrowser
Humidity rate and temperature supervision
MGE sensor for PDU (option)
Input / output
Voltage, frequency input & output / input current rating
230 V (Ph+N), 50/60 Hz / 16 A 
230 V (Ph+N), 50/60 Hz / 32 A (2 x 16 A single phase input)
Inlet type
1 x IEC 309 32 Amp male inlet 
2 x 16 A single phase input
2 m length cord
hard wired with strain relief coupling
Outlet type
12 x IEC 320 C 13, cable locking system 
12 x IEC 320 C 19, cable locking system, 
1 LED per outlet for local status supervision
Maximum current rating per outlet/per outlet group
10 A / 16 A max per each 6-outlet group
16 A / 16 A max per each 6-outlet group
Dimensions / Weight
Mounting mode 
rack mounting (0U), 2 removable flanges supplied 
horizontal rack mounting (2U), 2 mounting brackets supplied
(H x W x D) in mm / weight in kg
794 x 45 x 57 / 5.3 kg 
89 (2U) x 437 x 254 / 7.7 kg 
Switched PDU
5
6
4
3
2
1
Ampmeter PDU
1
2
5
4
8
1
7
6
5
3
4
2
6
7
9
5
2
7
11
2
9
3
4
Power input IEC 320 C 20 16 A male inlet 
(2 m cord  IEC 320 C 19 female/ FR-Schuko
male supplied)
Input current measurement digital display
Ethernet port for in-band supervision
Serial port for out-of-band supervision
2 RJ 11 ports for temperature/humidity
supervision
IEC 320 C 13 10 A outlet, (outlet cable
locking - system supplied)
Outlet status LED
Fuse (1 for each 6 outlet branche)
Terminal block connection with strain relief
coupling
IEC 309, 32 Amp male inlet. 2 m length cord.
IEC outlet C 320 C 19, 16 Amp
11
10
9
8
7
Safety standard, operating temperature, warranty 
CE, UL, TUV, 0°C to 50°C, 2 Years
8 NM 1U
16 V NM
12 NM 2U 
3
8
6
10
12 V