Bradford-White Corp BWCV User Manual

Page of 44
Internet Version for Reference Only
 
Bradford White
Page 20
Copper Brute II
Page 21
Most of the time, the number of stages from the 
external control will match the number of stages on the 
heater.  However, in some instances, the controller will 
not have enough staging capability to work with all of 
the stages on a heater (for instance, using an 8-stage 
external control with four 4-stage Copper Brute II 
units.)  In these instances, it is very important to follow 
the instructions in this section.  Figure 9 shows how to 
combine stages on the heater for those instances when 
the external controller cannot control all the stages 
available on the heater.
Note:  The only time heater stages should be 
jumpered is when the heater has an external control, 
and the heater is used in Mode 6.  In all other modes, 
when the heater controls its stages, the terminals 
shown in Figure 9 must NOT be jumpered.
SECTION 6.
Operating Instructions
6.1  Sequence of Operation
A call for heat can be initiated either 
automatically (“auto mode”) under thermostatic 
control by the heater temperature control, or by an 
external contact closure (“manual mode”).
In auto mode, the heater will fire its stages of 
input to maintain a target temperature programmed 
into the temperature control. The controller can be 
programmed per section 6.2.
In manual mode, an external control will control 
the heater stages, as long as the heater control is set to 
mode 6, and the auto/manual switch (located inside the 
control compartment) is set to manual.
The amber “Ready” light on the front panel 
indicates that the control system is energized. Upon a 
call for heat, the green “Heat” indicator on the front 
panel will light.
If the unit is pump-mounted, the pump will be 
energized. The pump terminals on the field-wiring 
terminals strip will energize a field pump that is 
properly interlocked with the heater. The green 
“Pump” indicator on the front panel will light.
Once the water flow switch makes, and if all of 
the safety interlocks are closed, the ignition module 
will energize the blower(s) for a 15-second pre-purge, 
followed by a 20-second period to allow the ignitor to 
heat.
Energizing the blower pressurizes the air box 
(which supplies air to the burners) and closes the 
normally-open contact(s) of the airflow pressure 
switch(es). This allows the ignition module to proceed 
with the ignition sequence.
The blocked flue pressure switch senses the 
pressure in the plenum. It will interrupt the airflow 
sensing circuit if this pressure exceeds a maximum 
value. If airflow is not proven, the ignition module  
will lockout.
The ignition module checks that the ignitor 
current has reached a minimum value and energizes 
the gas valve at the end of the ignitor heating period. 
The green “Stage 1” indicator on the front panel will 
light, indicating that the stage 1 gas valve is open. 
After a 4-second trial for ignition, the ignitor 
switches off, and unless a flame is detected by the 
flame sensor, the gas valve will close and the ignition 
module will either attempt ignition again (up to three 
times) or will lockout (if the optional lockout ignition 
module is used).
If flame is sensed, the burner will continue to 
fire as long as there is a call for heat. In Auto mode, 
additional stages are delayed by a minimum of 60 
seconds (less prepurge and ignitor warm-up time) and 
once energized, must fire for at least 30 seconds. The 
request for additional stages is indicated on the control 
display, and the energizing of additional burner stages 
is indicated by front panel lights.
If there is a subsequent loss of flame signal, the 
burner will attempt re-ignition up to three times (only 
once if optional lockout ignition module is used.)
When the call for heat is satisfied, the gas 
valve(s) closes and the blower(s) continues to run 
for 30 seconds. The pump will continue to run for a 
minimum of 20 seconds and up to a programmable 
maximum of 10 minutes.
If a call for heat is prevented from being satisfied 
either by a safety interlock or due to an ignition 
lockout, the red “Service” indicator on the front panel 
will light. To reset the standard ignition module, 
the reset button on the module must be pressed. 
Interrupting power to this module will not reset the 
lockout.
The Copper Brute II 1000 - 2000 models have 
two ignition modules that control different burners. If 
one module should fail for any reason, the remaining 
module can operate its burner(s) independently.
Important: The installer is responsible for identifying 
to the owner/operator the location of all emergency 
shutoff devices.
 WARNING
Do not use this appliance if any part has been 
under water. Immediately call a qualified service 
technician to inspect the appliance 
and to replace any part of the control system and 
any gas control that may have been 
under water.
6.2  Programming the Temperature 
Control
The same temperature control is used on all 
versions of the Copper Brute II (in two-and four-stage 
configurations), providing maximum flexibility to meet 
the needs of any system. Before start-up, you must 
program the temperature control for the type of system