Copper Brute II
Page 31
6.      Low water cutoffs, if installed, should be 
checked every 6 months. Float type low water 
cutoff should be flushed periodically.
7.      Inspect flue passages, and clean with brushes/
vacuums, if necessary. Sooting in flue passages 
indicates improper combustion. Determine the 
cause and correct.
8.      Inspect the vent system and air intake system, 
and if the vent system is Category III, ensure that 
all joints are sealed properly. If joints need to 
be resealed, completely remove existing sealing 
material, and clean with alcohol. Apply new 
sealing material, and re-assemble.
7.2  Appliance Maintenance and 
Component Description
Only genuine Bradford White replacement parts should 
be used.
 Caution
Label all wires prior to disconnection when servicing 
controls. Wiring errors can cause improper and 
dangerous operation. Verify proper operation after 
servicing.
See Figures 16 and 17 for location of gas train 
and control components.
Figure 16. Typical Gas Train Configuration.
Figure 17. Typical Control Panel.