Bradford-White Corp BWCV User Manual

Page of 44
Internet Version for Reference Only
 
Bradford White
Page 6
Copper Brute II
Page 7
the outdoors through horizontal ducts, each opening 
shall have a minimum free area of not less than 
1 square inch per 2000 Btu/hr (11 square cm/kW) of 
total input rating of all equipment in the enclosure. 
Table 3 shows data for this sizing method, for each 
Copper Brute II model.
Method 2: One permanent opening, commencing 
within 12 inches (30 cm) of the top of the enclosure, 
shall be permitted. The opening shall directly 
communicate with the outdoors or shall communicate 
through a vertical or horizontal duct to the outdoors 
or spaces that directly communicate with the outdoors 
and shall have a minimum free area of 1 square inch 
per 3000 Btu/hr (7 square cm/kW) of the total input 
rating of all equipment located in the enclosure. This 
opening must not be less than the sum of the areas of 
all vent connectors in the confined space.
Other methods of introducing combustion and 
ventilation air are acceptable, providing they conform 
to the requirements in the applicable codes listed 
above.
In Canada, consult local building and safety 
codes or, in absence of such requirements, follow CSA 
B149.1.
                                               Each Opening*
     Model               Square inches                Square cm
       500                         125                              807
       750                         188                             1213
      1000                        250                             1613
      1250                        313                             2020
      1500                        375                             2420
      1750                        438                             2826
      2000                        500                             3226
*Net Free Area in Square Inches / Square cm
Area indicated is for one of two openings; one at floor level and 
one at the ceiling, so the total net free area could be double the 
figures indicated.
This chart is for use when communicating directly with the 
outdoors. For special conditions and alternate methods, refer to 
the latest edition of ANSI Z223.1.
Note:  Check with louver manufacturers for net free area of 
louvers. Correct for screen resistance to the net free area 
if a screen is installed. Check all local codes applicable to 
combustion air.
Table 3. Combustion Air Openings.
2.1.2  Intake Combustion Air
The combustion air can be taken through the 
wall, or through the roof. When taken from the wall, 
it must be taken from out-of-doors by means of the 
Bradford White horizontal wall terminal (see Table 1). 
When taken from the roof, a field-supplied rain cap or 
an elbow arrangement must be used to prevent entry of 
rain water (see Figure 2).
    Use single-wall galvanized pipe, per Table 
4, for the combustion air intake (see Table 1 for 
appropriate size). Route the intake to the heater as 
directly as possible. Seal all joints with tape. Provide 
adequate hangers. The unit must not support the 
weight of the combustion air intake pipe. Maximum 
linear pipe length allowed is 50 feet (15.2m). Three 
elbows have been calculated into the 50-foot (15.2m) 
linear run. Subtract 10 allowable linear feet (3.0m) for 
every additional elbow used (see Table 1). When fewer 
than 3 elbows are used, the maximum linear pipe 
length allowed is still 50 feet (15.2m).
     Term                                   Description
      Pipe          Single-wall galvanized steel pipe, 24 gauge
                       minimum (either insulated or non-insulated)
      Joint              Permanent duct tape or aluminum tape
    Sealing
Table 4. Required Combustion Air Piping Material.
The connection for the intake air pipe is on 
the filter box. The heaters may have venting and 
combustion air ducting attached to the top or the back. 
They are shipped with the connections at the top. For 
attaching either or both pipes to the back, the mounting 
flanges are reversible by removing the mounting 
screws and orienting the flanges in the desired 
position. Replace the screws after positioning flanges. 
Run a bead of silicone around the collar and slide the 
pipe over the collar. Secure with sheet metal screws.
In addition to air needed for combustion, air 
shall also be supplied for ventilation, including all air 
required for comfort and proper working conditions 
for personnel. The Copper Brute II loses less than 1 
percent of its input rating to the room, but other heat 
sources may be present.
Figure 2. Combustion Air and Vent Through Roof.