Bosch Appliances Smoke Alarm FPD-7024 User Manual

Page of 122
inhibited (but alarm monitoring continuing), the system indicates SYSTEM TROUBLE,
RMT PRG ACTIVE during remote programming. Sounders do not activate during this mode, but
other outputs programmed for Zone 62, general system trouble, do activate.
Trouble conditions that occur during a remote programming session are not annunciated at
the control panel until the remote programming session ends. These conditions are available
in the remote programmer diagnostic displays during the session. Alarm conditions terminate
remote programming and are shown immediately.
When remote programming is disabled, you can still connect to the control panel for
diagnostics and view the existing programming (except PIN numbers). To actually change
programming, enable remote programming.
To enable remote programming, refer to the following programming items:
0-3-7 Remote Programming, 67
0-6-6 Machine Bypass, 85
An access code with maximum authority (1) is needed to begin remote programming from the
panel.
58
en | Programming
Fire Alarm Control Panels
2012.08 | 04 | F01U008458
Installation and Operation Manual
Bosch Security System, Inc.