Bosch Appliances Smoke Alarm FMM325A Leaflet

Page of 2
2 | FMM‑325A Series Analog Manual Stations
Parts Included
Quant.
Component
1
Manual station
1
Point Contact Module
1
FMM‑100GR Scored Acrylic Breakrod
1
D102 Key (#1358)
1
Literature pack
Technical Specifications
Electrical
Current
Alarm:
28 mA
Polling:
22 mA ± 20%
Standby:
0.35 mA typical
Voltage
Input:
24 VDC nominal
Operating:
17 VDC to 41 VDC
Environmental Considerations
Temperature (operating):
+14°F to +120°F
(-10°C to +49°C)
Mechanical Properties
Activation Force:
5 lb (2.3 kg)
Dimensions (H x W x D):
4.75 in. x 3.2 in. x 0.875 in.
(12.1 cm x 8.1 cm x 2.2 cm)
Material:
Painted die‑cast metal
Ordering Information
FMM‑325A Single‑action Manual Station
Communicates with the FPA‑1000‑UL,
D9024, D8024, and D10024A FACPs (both
power and data) over a two‑wire polling circuit
FMM-325A
FMM‑325A‑D Double‑action Manual Station
Communicates with the FPA‑1000‑UL,
D9024, D8024, and D10024A FACPs (both
power and data) over a two‑wire polling circuit
FMM-325A-D
Accessories
D102 Replacement Key
Replacement key (#1358) for the D101 lock.
D102
FMM‑100BB‑R Surface‑mount Back Box
(red)
Red cast‑metal back box
FMM-100BB-R
FMM‑100GR Scored Acrylic Break Rods
Scored acrylic rods (12 per package)
FMM-100GR
Americas:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5600 JB Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com
Asia-Pacific:
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6258 5511
Fax: +65 6571 2698
apr.securitysystems@bosch.com
www.boschsecurity.com
Represented by
© Bosch Security Systems Inc. 2010 | Data subject to change without notice
T1899690379 | Cur: en-US, V9, 4 Jul 2010