Bosch Appliances Smoke Alarm D2071A User Manual

Page of 28
13
Bosch | 09/04 | 74-06200-000-F
2.4.2
Wiring
Connect only low voltage power sources and devices to
Terminals 16, 17, and 18. Do not use the D2071A
Standby Battery to provide a power output for the
circuit.
2.5
Phone Line Trouble Relay
Use Terminals 13, 14, and 15 for Phone Line Trouble
Relay connections.
To use the optional Phone Line Trouble Relay, install a
D136 Relay in socket K5. The D136 has a Form “C” dry
contact, rated at 2 A maximum current at 30 VDC
(power from independent supply). The relay activates
(reverse state) when a faulted condition appears on either
the primary or alternate telephone lines, or when a
communication failure occurs.
The Phone Line Trouble Relay activates whenever the
Phone Line Trouble Buzzer sounds. Refer to 
Section 1.8.6
Phone Line Trouble Buzzer on page 7 
for details on relay
activation and restoral.
2.5.1
Installation
To install a D136 Relay into the K5 socket (labeled
“TROUBLE RELAY”):
1.
Slide back the D2071A cover.
2. Place the relay into the socket with the pins oriented
as shown in Item 1 in Figure 7.
3. Install the relay flush left or right.
2.5.2
Wiring
Terminal 14 is the common (C) terminal.
Terminal 13 is the normally closed (NC) terminal.
Terminal 15 is the normally open (NO) terminal.
In a normal state, Terminals 13 and 14 have continuity.
When activated, Terminals 14 and 15 have continuity.
Only connect the low voltage power sources and devices
to Terminals 13, 14, and 15.
 
Do not use the D2071A standby battery to 
supply power for the circuit. In some slave 
communicator applications, the Phone Line 
Trouble Relay (Terminals 13 to 15) on the 
D2071A can be connected to a trouble  
zone input on the FACP. 
 
2.6
Primary Power Supply
 
Use Terminals 1 and 2 for primary power 
supply connections. 
 
Power the D2071A Control Panel using a 12 VAC or
20 VA transformer and standby battery. You can also
connect the D2071A to the 24 VDC output of an FACP.
Use either method for NFPA 72 applications.
 
Do not connect the D2071A to a 12 VDC 
power supply of an existing FACP. Use the 
transformer and battery for 12 VAC Mode. 
 
Parallel Activation on Powerup: The Phone Line
Trouble Buzzer, Phone Line Trouble Relay, and Phone
Line LED briefly activate on AC or battery powerup to
indicate the DACT is operational.
2.6.1
12 VAC Mode
Connect a 12 VAC, 20 VA transformer to Terminals 1
and 2 using 18 AWG (1.2 mm) stranded wire, maximum
length 50 ft (15.3 m). Commercial fire applications
require the D8004 Transformer Enclosure for the D1220
Transformer or the D2071AmC Kit.
 
The hardwire transformer mounted in the 
D4103R Enclosure, included in the 
D2071AC Kit, replaces the D1220 
Transformer. Ensure the 110 VAC or  
120 VAC power source is turned off when 
connecting the black and white transformer 
leads to the source. Connect the yellow 
leads from the transformer to Terminals 1  
and 2. 
 
D2071A  | Operations & Installation Guide | 2.0    Installation
K6
K5
18
17
16
15
14
13
12
11
10
1
2
1 - Trouble relay
2 - Alarm relay
Figure 7:
Relay Sockets