Bosch Appliances Smoke Alarm D2071A User Manual

Page of 28
15
Bosch | 09/04 | 74-06200-000-F
Restoral ZN 9 Exceptions: If a battery is not connected
to the D2071A when AC power is connected, the control
panel sends a RESTORAL ZN 9 Report to the receiver.
A RESTORAL ZN 9 is also sent after the programmer
disconnects from the D2071A.
Charging Circuit
The D2071A charges the battery with a float charge
circuit using a maximum charging current of 300 mA.
The battery discharge and recharge schedule (Table 5)
shows voltages during the discharge and recharge cycles.
2.7.2
12 VAC Battery Discharge and Recharge
Schedule
Refer to Table 5 for the 2 VAC battery discharge and
recharge schedule.
2.8
Telephone Connections
2.8.1
Telephone Cord Installation
Use a D161 or D162 Phone Cord to connect the primary
telephone line to the D2071A Modular Jack ( J1). Use a
second D161 or D162 Phone Cord to connect the
alternate telephone line to the D2071A Modular Jack
( J2).
 
For all applications, you must connect 
separate primary and alternate telephone 
lines to the D2071A. 
 
2.8.2
Location
To prevent the jamming of alarm and other reports, wire
and locate the RJ31X or RJ38X jack so normal
telephone use is temporarily interrupted while the
communicator transmits data (Figure 8). After
installation, confirm the D2071A seizes the line,
acquires dial tone, and correctly reports to the receiver.
2.8.3
Telephone Line Supervision
The D2071A monitors both the primary and alternate
telephone lines while the communicator is idle by
sniffing the line for trouble. Telephone line trouble is
line voltage below 10 VDC with a current less than
10 mA. If there is a report waiting to be transmitted, the
D2071A does not sniff the telephone lines until the
report is transmitted or a communication failure occurs.
The D2071A reports a faulted condition on the primary
telephone line as a TROUBLE ZN B and the alternate
telephone line as a TROUBLE ZONE C.
Each line is sniffed once a minute if both lines are good.
If a line is determined to be in trouble, the D2071A
steps up the test rate and sniffs once every 10 sec. If the
trouble still exists after 15 samples (150 sec), the control
panel sends a Trouble Report and activates the buzzer,
Phone Fail LED, and Phone Line Trouble Relay (if
installed). Ref
er to
 Section 2.5 Phone Line Trouble Relay
on page 13 
for installation instructions.
The buzzer, LED, and relay deactivate after a trouble
condition on the telephone line when the receiver
acknowledges the Phone Line Trouble Report, or when
the line returns to normal. If the D2071A attempts to
transmit the Phone Line Trouble Report ten times
without acknowledgment from the receiver, a
communication failure occurs.
If the D2071A is in communication failure, either the
primary and alternate telephone lines must be detected
as normal and a report acknowledged by the receiver
before the buzzer, LED, and relay deactivate.
D2071A  | Operations & Installation Guide | 2.0    Installation
R1
T1
1
2
3
4
5
6
7
8
R
T
1
4
3
2
Figure 8:
RJ31X Wiring
1 - Premises phone
3 - Full modular phone jack
2 - RJ31X  Module
4 - Incoming Telco line
Table 5:
12 VDC Battery Discharge and Recharge
Schedule
 
Discharge Cycle 
13.8 V 
FACP battery float voltage 
11.8 V 
Battery Trouble Report (TROUBLE ZN 9) 
8.5 V 
Disables all processing and memory functions. 
Deep battery discharge can occur below this 
level. 
Recharge Cycle 
AC on 
Battery recharging begins 
9.0 V 
Battery Trouble Report (only if the battery is  
discharged below 8.5 V) 
13.4 V 
Battery Restoral Report (RESTORAL ZN 9) 
13.8 V 
Battery charged 
Notes: 
1.
 
The source supervised is the battery connected to the 
D2071A. 
2.
 
Actual voltage can vary 
±
15.