Bosch Appliances Smoke Alarm D2071A User Manual

Page of 28
21
Bosch | 09/04 | 74-06200-000-F
PriPh# 
 
 
Default: 
Blank 
Selections:  0 to 9, B to F, or Blank 
 
Use to select the primary receiver telephone number.
You can enter up to seven characters. Refer to Table 9 for
other dialing character selections.
 
When programming the primary and 
alternate telephone numbers, ensure the 
primary telephone number is different from 
the alternate telephone number. 
 
AltPri 
 
 
Default: 
Blank 
Selections:  0 to 9, B to F, or Blank 
Blank 
No prefix or area code. A delay of 
up to 7 sec is automatically inserted 
in front of the prefix. 
 
Use to select the prefix for the alternate receiver
telephone number. You can enter up to nine characters.
Refer to Table 9 for other dialing character selections.
AltPh# 
 
 
Default: 
Blank 
Selections:  0 to 9, B to F, or Blank 
Use to select the alternate receiver telephone number.
You can enter up to seven characters. Refer to Table 9 for
other dialing character selections.
 
When programming the primary and 
alternate telephone numbers, ensure the 
primary telephone number is different from 
the alternate telephone number. 
 
12 V Mode 
 
 
Default: 
Yes 
Selections:  Yes or No 
Yes 
12 VAC, 20 VA, 60 Hz transformer 
operation. 
No 
24 VDC supply from an existing 
FACP. 
Use to enable either the 12 V Mode or 24 V Mode.
Class B Mode 
 
 
Default: 
Selections:  1 to 3 
Mode 1 not acceptable for 
stand-alone applications. 
Mode 2 has restricted use for 
stand-alone applications. 
Mode 3 is required for most 
stand-alone applications. 
Use to program the operating mode for the Class “B”
Supervisory Circuits (Zones 2 and 3).
For detailed mode specifications, refer to Section 2.3
Zones 2 and 3, Supervisory Circuits
 beginning on page 11
for installation instructions.
Retard Time 
 
 
Default: 
Selections:  0 to 90 
 
Use to program the retard timer for the Class “A” Alarm
Initiating Circuit (Zone 1). Enter the number of seconds
you want for the retard time. After an alarm condition is
detected on the sensor loops, the retard timer starts. An
Alarm Report is not transmitted until the retard timer
reaches the value entered in Retard Time. If the faulted
condition restores before the retard timer reaches the
value entered in Retard Time, the Alarm Report is not
transmitted.
Refer to 
Section 2.2.2 Retard and Reset Times on pages 10
and 11 for details.
 Refer to the appropriate NFPA
Standard or the local AHJ for acceptable retard times.
Table 9:
Special Dialing Characters
 
Selection 
Dialing Effect  
Description 
(*) character 
Accesses special 
telephone features. 
3-sec pause 
While dialing, inserts a  
3-sec pause between 
digits. 
7-sec dial tone 
wait 
Waits up to 7 sec for a 
dial tone before dialing. 
(#) character 
Accesses special 
telephone features. 
Alternates 
between 
rotary and 
DTMF 
Used when accessing 
some long-distance 
carriers while using 
rotary-dial phone lines. 
 
D2071A  | Operations & Installation Guide | 4.0    Program Record