Bosch Appliances Smoke Alarm D9124 User Manual

Page of 4
D9124 Addressable Fire Alarm Control Panel (FACP) | 3
Category
Product ID
Product Description
D192G
Bell supervision module
D8125
POPEX module
D8125MUX
Zonex to dual multiplex interface
D8128D
OctoPOPIT module
D8129
Octo-relay module
D8130
Release module
D9127U
POPIT module (no tamper)
D9127T
POPIT module (tamper)
D9131A
Parallel printer interface module
DX4020
Ethernet interface module
Programming
Products
D5200CE
Handheld programmer
RPS
Remote Programming Software
RPS-LITE
Remote Programming Software
RPS-INTL
Remote Programming Software
Parts Included
The D9124 Addressable Control Panel is shipped in three
boxes. One box contains:
Quant.
Component
1
D9412GLTB Control Panel (less terminal blocks)
Another box contains:
Quant.
Component
1
D9101 Enclosure Assembly with Door
The third box contains a D9100 Accessory Module Carrier
that includes the following:
Quant.
Component
2
D192C Indicating Circuit Supervision Modules
1
D928 Dual Phone Line Switcher
1
D8125 POPEX Module (additional optional)
1
D9142LC 24 VDC Power Supply
The third box also contains:
Quant.
Component
1
D1256 Fire Alarm Keypad
1
D1601 Transformer
1
Wiring Harness
1
Wiring Harness for the D8125 POPEX Module
2
560 Ω Resistors (for D192C Modules)
2
D161 Dual Modular Telephone Cords
1
D162 Dual Modular Telephone Cord
1
Literature pack
Technical Specifications
Environmental Considerations
Relative Humidity:
Up to 85%; non-condensing
Temperature (operating):
+32°F to +122°F (0°C to +50°C)
Inputs
Sensor Circuits:
Up to two 8125 POPEX modules,
119 addresses per module
Sensor Circuit Protection:
Power limited to 4 A; short circuit, reverse
polarity, thermal overload and current over-
load protection on-board
Sensor Loop Technology:
Four-wire addressable circuits
Mechanical Properties
Color:
Red
Material:
16-gauge (1.5 mm) steel
Dimensions (H x W x D)
Enclosure Box:
36.1 in. x 22.1 in. x 3.2 in.
(92 cm x 56 cm x 8.1 cm)
Removable Door:
37.1 in. x 23.3 in. x 1.1 in.
(94 cm x 59 cm x 2.8 cm)
Outputs
Off-board relays:
Up to 16 optional D8129 Relay Modules (eight re-
lay outputs per module)
On-board NACs:
Two; 1.8 A maximum per circuit
Power Requirements
Current (operating)
Alarm + sensor load:
874 mA
Idle:
412 mA
Power (auxiliary):
24 VDC nominal at 1.8 A
Power (primary):
120 VAC, 60 Hz, 360 VA
Ordering Information
D9124 Addressable Fire Alarm Control
Panel (FACP)
Up to eight supervised or 32 unsupervised re-
mote annunciators
D9124
Accessories
D113 Battery Lead Supervision Module
Supervises wiring connections for two 12 V
batteries connected to the same set of charging
terminals.
D113
D122 Dual Battery Harness
Harness with circuit breaker. Connects two
batteries to a compatible control panel.
D122
D135A Low‑battery Disconnect Module
Disconnects the control panel from the battery
when the battery level drops to 9.5 VDC.
D135A
www.boschsecurity.com