 Panel 
Programming 
 
 
D7024 Operation and Installation Guide 
 
© 2005 Bosch Security Systems 
Page 51 
41740F 
 
These menu items are only allowed at the local keypad. 
The following window will appear: 
OPTION BUS (M/M) 
1-  
UPDATE BUS 
2-  
SETUP KEYPDS 
Press [1] to program system to update bus. After you have programmed Update Bus, the following window will appear:  
UPDATE COMPLETE 
TOT BUS DEVS: X 
Then the previous window will appear. 
7.3.3.2 Setup 
Keypad 
 
Shortcut: 0-
PROG
, 3-
PROG SYSTEM
, 4-
OPTION BUS
 
This feature tells the system how many keypads should be supervised. It automatically performs an update bus operation 
as it completes. 
OPTION BUS 
1-  
UPDATE BUS 
2-  
SETUP KEYPDS 
Press [2] to set up keypads. The following window will appear: 
# OF KEYPADS (__) 
(0-4): ____ 
Enter the desired value and press [#]. The current setting is displayed in parentheses on the first line. After you set up the 
keypads, the update bus operation proceeds (see above), then the previous window will display. 
7.3.4 PIN 
REQUIRED 
7.3.4.1 Local 
 
Shortcut: 0-
PROG
, 3-
PROG SYSTEM
, 5-
PIN REQUIRED?
 
A PIN can be required before operations can be performed using the local, built-in keypad.  
The following window will appear: 
PIN REQUIRED? 
1-  
LOCAL 
2-  
REMOTE 
Press [1] to require a PIN at the local keypad. The following window will appear: 
LOCAL KEYPD PIN? 
____:YES(1)NO(2) 
Press the number key that corresponds to your selection. The current setting is displayed in front of the colon on the 
second line. After making your selection, the previous window will display. 
7.3.4.2 Remote 
 
Shortcut: 0-
PROG
, 3-
PROG SYSTEM
, 5-
PIN REQUIRED?
 
The following window will appear: 
PIN REQUIRED? 
1-  
LOCAL 
2-  
REMOTE