3.2.3 
Ademco 4-1 Express (Message Type b) 
SIA Mode Description 
4-1 Express 
Example 
<LF><CRC><b><sequence#><receiver#><line#>[#aaaa|X]<CR> 
 
Table 41: 
Ademco 4-1 Express (Message Type b) Byte Description 
 
Title Description 
LF 
Standard line feed character.  
CRC 
Cyclical redundancy check number.  
Message Type 
b  
sequence# 
The message sequence number. The valid sequence number range is 0001 to 9999. 
receiver# 
The receiver gateway that sent the message. Valid digits are 01 to 99 for the 
D6600/D6100. 
line# 
(Line/Group #) 
The line number of the line in the receiver gateway that sent the message. Valid digits are 00 
to 99. The receiver uses Line 0 (zero) for internal messages. 
account# 
The communicator's account number has four digits. 
Zone number  
 
Figure 9: 
Message sent to printer 
mm/ddshh:mmsLxxsE41sACCTsaaaasEVENT=X
 
 
 
For lines that are grouped, Gxx appears 
instead of Lxx. 
 
Table 42: 
Ademco 4-1 Express (Message 
Type b) Printer Output 
 
Characters Description 
E41 
Ademco 4-1 Express format. 
Lxx:  
Line number. 
Gxx 
Grouped line numbers.