Bosch Appliances Network Card D8125INV User Manual

Page of 40
 D8125INV 
 Installation 
 
 D8125INV Operation and Installation Guide  
 
© 2005 Bosch Security Systems 
Page 27 
49690E  
 
2. 
The keypad will then display the following menus (if there are 
no system faults on the D8125INV): 
 
See step 4 below  
 
See step 5 below  
 
3. 
If [1] is pressed, this menu allows you to jump to any RF point 
programmed into the D8125INV. If [1] is pressed from this 
menu, the keypad will display: 
 
 
 
4. 
After a valid RF Point Number is entered, Figure 18 will be displayed. 
Item 
Variable 
Description 
xxx 
D8125INV has not received 
at least 30 transmissions to 
determine signal strength 
  
Bad 
Transmitter 
must 
be 
relocated 
 
 
OK 
Good signal strength 
2 <value> 
Normal 
  
Faulted 
  
Tamper 
  
Missing 
  
Low 
Bat 
  
Tamper, 
Low 
Bat 
 
 
Faulted, Low Bat 
 
Figure 18: Point Number Status 
Table 10: Variable Descriptions 
 
If an invalid RF Point Number is entered, the following is 
displayed: 
 
If the D8125INV is connected to Zonex 1, enter point numbers 
9-127 (or 9-75 if D7412G, D7412, D7412GV2, D7212, D7212G, 
or D7212GV2 ).  
 
Figure 19: RF Point not 
programmed 
 
 
Points 74 and 75 and Points 194 and 195 are reserved for the FA113 Keyfob. 
 
If the D8125INV is connected to Zonex 2, enter point numbers 129-247. After entering the point 
number and pressing the [ENT] key, the keypad will display Figure 18.