Bosch Appliances Network Card D8125INV User Manual

Page of 40
 D8125INV 
 Troubleshooting 
 
 D8125INV Operation and Installation Guide  
 
© 2005 Bosch Security Systems 
Page 31 
49690E  
 
Symptom 
Diagnosis 
Remedy 
RF Keyfob transmitter points go 
missing 
RF keyfobs may only be 
programmed as points 74 & 75, or 
as points 194 & 195.  Since keyfobs 
can be carried off-site, these points 
are not supervised, regardless of 
the programmed RF supervision 
interval. 
Reprogram RF keyfob transmitters 
as Points 74 & 75 (zonex 1), or 
Points 194 & 195 (zonex 2). 
RF points go missing when 
programmed supervision interval 
= none. 
These RF Points are programmed 
as Fire Points (transmitter modes 
8-12).  Transmitters programmed 
as Fire points will be supervised at 
4 hour intervals, regardless of 
programmed supervision interval 
time. 
If those RF points are not for Fire 
devices, connect and reprogram 
the transmitter as new, changing 
the transmitter Mode to non-fire 
(Modes 1-7). 
Table 11: Troubleshooting Solutions 
4.1 
FA400 Receiver Supervision 
The D8125INV supervises the Inovonics FA400 receiver by periodically polling it. 
If the FA400 does not respond to the polls over a five minute period, the 
D8125INV will initiate a Point Bus Trouble event back to the control panel. The 
control panel will then initiate a Point Bus Fail 1 (or 2) event. 
If this occurs, the D8125INV will display Figure 20. 
 
Figure 20: Call for Service,  
Enter Code + ENT 
Enter a valid passcode and then Figure 21 will be displayed. 
 
Figure 21: Call for Service, Receiver 
Missing 
4.2 
Missing Transmitters  
A transmitter may go missing in the system due to the following most common 
reasons: 
 
dead battery 
 
physical environmental changes  
 
damage to the transmitter 
The D8125INV will display Figure 22. 
 
Figure 22: Call for Service,  
Enter Code + ENT 
Enter a valid passcode and then Figure 23 will be displayed. 
Note: 
The number 019 (which is used as an example) refers to the actual 
quantity of points missing, not the specific point number. 
 
Figure 23: Call for Service, Receiver 
Missing 
4.3 
Low Transmitter Battery Conditions 
When the transmitter reports low battery conditions and replacement is necessary be sure to press reset button on 
transmitter after replacing battery. Also, be sure to test the transmitter for proper operation after replacing battery.