Bosch Appliances Network Card D8125INV User Manual

Page of 40
 D8125INV 
 Overview 
 
 D8125INV Operation and Installation Guide  
 
© 2005 Bosch Security Systems 
Page 9 
49690E  
 
2.0 D8125INV 
Overview 
2.1 Features 
 
Compatible with Bosch Security Systems D9412GV2, D7412GV2, D7212GV2, D9412G, D7412G, D7212G, 
D9412, D7412, D7212, and D9112 Control Panels. (FA113 can not be used on the D7212GV2 andD7212G  
panels) 
 
Menu driven User Interface 
 
On the D9412GV2, D9412G, D9412, and D9112, the D8125INV supports up to 2 Inovonics FA400 
Receivers (with a maximum of 238 transmitters [119 per bus]) 
 
On the D7412GV2, D7412G, and D7412, the D8125INV supports up to 2 Invonics FA400 Receivers (with a 
maximum of 67 transmitters) 
 
On the D7212GV2 and D7212G, the D8125INV supports up to 2 Invonics FA400 Receivers (with up to 32 
transmitters in the same location). 
 
An unlimited number of FA113 Wireless Keyfobs can be added 
 
Used for diagnostic functions to troubleshoot system RF Transmitters 
 
Programmable system-wide supervision time interval and individual transmitter check-in time 
 
Programmable transmitter configuration (Normally Open/Normally Closed, Internal/External Contact, 
EOL Resistor) 
2.2 Specifications 
LCD Display 
2 lines by 16 characters, Backlit 
User Interface: 
Keypad 
0 – 9 numbers 
ESC, ENT, PREV, NEXT and DIAG keys 
Operating Voltage: 
10.2 - 14 VDC supplied by Aux Power from Control Panel or an External 
Auxiliary Power Supply. 
Current: 
30 mA typical, 45 mA maximum 
plus 
 40 mA for each FA400 receiver 
Operating Temperature: 
+32
°
F to +149
°
F (0
°
C to +65
°
C), 93% Relative Humidity 
Wiring: 
18 AWG or 22 AWG Solid or Stranded. Maximum distance from control 
panel cannot exceed 5 ft. (1.5 m). 
Dimensions (HxWxD): 
3.94 in. x 6.5 in. x 1.2 in. (10 cm x 16.6 cm x 3 cm) 
Weight: 
8.6 oz. (243 g) 
Table 3: D8125INV Specifications 
Operating Voltage: 
10.2 VDC to 14 VDC 
Curent: 
40 mA Max. 
Wiring: 
18 AWG or 22 AWG Solid or Stranded. Maximum distance from D8125INV 
to FA400 cannot exceed 200 ft. (61 m) or 1000 ft. (305 m) with power supply. 
Table 4: FA400 Specifications 
2.2.1 Power 
 
If the D8125INV is powered down and then back up, it may take up to a maximum of 5 minutes (up to 15 
minutes for 5 minute Transmitter Check-In Time) for all the transmitters to report back to the D8125INV 
with their current status. On systems employing fewer transmitters, this time is reduced proportionately. 
In addition, when the D8125INV is powered up, all programmed RF points will report Normal until their 
state is updated. 
The D8125INV power should be connected to the control panel using the Aux Power terminals. If the D8125INV were to 
lose power, the following conditions may result: 
 
All RF points will report to the control panel as missing (trouble/alarm)