Bosch Appliances Network Card C900V2 User Manual

Page of 28
Conettix C900V2 | Installation Guide | 3.0  
Setup 
 
 
Bosch Security Systems, Inc. | 8/08 | F01U087780-01
 
2.7 Ethernet 
Connection 
One of the RJ-45 jacks connects the C900V2 to 
the Ethernet Network (LAN or WAN). 
The connector pins are listed in Table 3. 
 
Table 3: 
Ethernet Connector Pins 
 
Pin Connection 
TX+ 
2 TX– 
RX+ 
RX– 
 
3.0   Setup 
3.1 Setting 
P3 
A shorting link on P3 selects the voltage and 
current applied to the alarm panel’s telephone 
circuit to simulate the signal from a PSTN 
telephone exchange. For most alarm panels, set 
the shorting link to the H position (short the middle 
and right pins of P3). The L position results in 
slightly lower power consumption for the C900V2 
but some alarm panels might report a telephone 
line failure when dialing the C900V2. 
 
 
For UL approved applications, the 
shorting link must be set to the H 
position. 
 
 
3.2 
Setting the DIP Switches 
A ten-position DIP switch programs the C900V2. 
The programming depends on the application and 
dialer format of the control panel connected to the 
module.  
 
Figure 8:  C900V2 DIP Switches 
1
2
3
4
5
6
7
8
9
10
1
2
O
N
1 –  Off 
2 –  On 
 
Because the C900V2 emulates a phone 
line and a digital receiver, you must 
program the C900V2 to the format it 
receives from the control panel. 
 
DIP Switch positions 1 through 4 and 10 program 
the dialer format into the C900V2. Table 4 on page 
9 lists the format programming for these DIP 
switches.