ICP-CC404 | Installation Guide | 15.0   System Reporting Information 
 
 
60 Bosch 
Security 
Systems, 
Inc. | 12/08 | F01U089401-02
 
Example 
All eight zones are programmed for lockout dialer 
with a Swinger Shutdown Count of 6. If Zone 1 
activates an alarm, the Swinger Shutdown Count 
decreased to 5 when the control panel calls.   
If Zone 1 reactivates the dialer, the Swinger 
Shutdown Count is decreased to 4. If Zone 1 
reactivates the dialer three more times, the Swinger 
Shutdown Count is 1. 
If Zone 2 activates an alarm, the Swinger Shutdown 
Count decreases to 0, which locks out Zone 2 from 
activating the dialer until the system resets. At this 
point, the Swinger Shutdown Count for the Dialer 
resets to 6 and the process of swinger shutdown for 
the remaining zones, including Zone 1, begins again 
until all zones are locked out. 
15.0  System Reporting 
Information 
This section covers basic housekeeping features of the 
system.  
15.1  Zone Status – Bypass Reports 
Program the Zone Bypass Report value in 
Location 
325 (the default value is 9) and the Zone Bypass 
Restore Report value in 
Location 326 (default 8). 
A zone is bypassed when it is manually isolated. 
Refer to Section 4.11 Isolating Zones on page 21 for 
information on isolating zones. A Zone Bypass 
Report (Contact ID Event Code 570) is sent at the 
end of Exit Time for any zone that was manually 
isolated. A 24-Hour Zone sends a Zone Bypass 
Report when the zone is selected to be isolated. 
A Zone Bypass Restore Report is sent when the 
system is disarmed. All bypassed zones are cleared 
when the system is disarmed. 
The Bypass Code parameter is used as the expansion 
digit in 4+2 Formats. It has no effect on Contact ID 
Format because a Zone Bypass is always sent as 
Event Code 570. 
 
 
If Zone Bypass Reports are not required, 
program Locations 325 and 326 as 0. 
 
15.2  Zone Status – Trouble Reports 
Program the Zone Trouble Report value in 
Location 327 (the default value is 2) and the Zone 
Trouble Restore Report value in 
Location 326 
(default 
3). 
A zone is in trouble when it is unsealed at the end of 
Exit Time. A Sensor Trouble Report (Contact ID 
Event Code 380) is sent to indicate that one or more 
zones were automatically isolated by the system. 24-
Hour Zones that are unsealed at the end of Exit Time 
do not send a Sensor Trouble Report because the 
restore for that zone is still outstanding. 
A Sensor Trouble Restore Report is sent for Burglary 
Zones when the zone is resealed or the next time the 
system is disarmed (whichever happens first). A 24-
Hour Zone sends a restore signal only when it is 
resealed.  
The Trouble code parameter is used as the expansion 
digit in 4+2 Format. It has no effect on Contact ID 
Format because a Sensor Trouble Report is always 
sent as Event Code 380. 
 
If Sensor Trouble Reports are not 
required, program Locations 327 and 
328 as 0. 
 
15.3  Zone Status – Sensor Watch 
Reports 
Program the Sensor Watch Report value in 
Location 329 (the default value is 4) and the Sensor 
Watch Restore Report value in 
Location 326 
(default 
8). 
A Self Test Failure Report (Contact ID Event Code 
307) is sent to the base station receiver when a zone 
was not activated during the Sensor Watch Time 
programmed in Locations 408 and 409 (refer to 
Section 17.7 Sensor Watch Time on page 71). This report 
continues to be sent (according to the frequency of 
the Sensor Watch Time) until the fault is corrected.  
To clear the fault and stop any additional reporting, 
you must unseal and reseal the zone that registered 
the fault. Use the Sensor Watch Time in Locations 
408 and 409 to set the number of days a zone can 
remain sealed without registering a fault. Refer to 
Section 14.3.4 Zone Options 1 on page 57 to select zones 
to be monitored by the Sensor Watch feature. 
 
If Self Test Failure Reports are not 
required, program Locations 329 and 
330 as 0. 
 
15.4  Zone Status – Alarm Restore Code 
Program the Alarm Restore Code value in 
Location 331. 
The default value is 
14. 
If Zone Alarm Restore Reports are required, program 
this location as 14. If not, program this location as 0.