ICP-CC404 | Installation Guide | 16.0   Programmable Outputs 
 
 
Bosch Security Systems, Inc. | 12/08 | F01U089401-02 
65
 
Example 
3,0 Communications Failure 
This event operates after the dialer makes all possible 
attempts to reach the base station receiver. It resets 
when the control panel receives the first kiss-off. This 
Output Event Type is not applicable to domestic 
reporting. 
To redirect this Output Event Type to operate a 
codepad buzzer, program the Output Event Type as: 
11,0 Communications Failure  
The codepad buzzer now operates instead of the 
output that was programmed. Output 3 is no longer 
functional and cannot be used for any other Output 
Event Type.  
16.2  Output Event Types 
There are approximately 60 Output Event Types. 
Two numbers designate each Output Event Type. 
Program these numbers into the appropriate locations 
for the output. 
 
 
All reset times reference Polarities 1 and 
8. Reset times vary depending on the 
selected polarity. 
 
0,0 
EDMSAT - Satellite Siren (Output 1 Only) 
This output controls all functions of the SS914 
Satellite Siren (EDMSAT). The Speaker Indication 
Beeps option does not function through the satellite 
siren for remote operations. No polarity is required 
for this Output Event Type. 
0,1 System 
Armed 
This output operates when the system is armed. The 
output resets when the system is disarmed.   
0,2 System 
Disarmed 
This output operates when the system is disarmed. 
The output resets when the system is armed.   
0,3 
Armed in STAY Mode 
This output operates when the system is armed in 
STAY Mode 1 or STAY Mode 2. The output resets 
when the system is disarmed. 
0,4 
Armed in AWAY Mode 
This output operates when the system is armed in 
AWAY Mode. The output resets when the system is 
disarmed.   
0,5 
Auto Arm Pre-Arming Alert Time 
This output operates during the time period before 
the control panel is automatically armed in AWAY 
Mode or STAY Mode 1. The output resets when the 
control panel is automatically armed in AWAY Mode 
or STAY Mode 1. The Auto Arming Pre-Alert Time 
is programmed in Location 413 (refer to Section 17.11 
on page 72 for more information). 
0,6 
Exit Warning with All Zones Sealed or Entry 
Warning 
This output operates during Exit Time when the 
control panel is armed and all zones are sealed. The 
output resets when Exit Time expires.  
This output operates again during Entry Time and 
resets when Entry Time expires or the system is 
disarmed.  
This output also operates if a zone is activated when 
the system is armed in STAY Mode 1 or STAY Mode 
2 and the Entry Guard Timer for STAY Mode is 
programmed in Locations 404 and 405 (refer to 
Section 17.5 on page 71). 
0,7 Exit 
Warning 
This output operates during Exit Time when the 
system is armed. The output resets when Exit Time 
expires. 
0,8 Exit 
Warning 
Finished 
This output operates after Exit Time expires when the 
system is armed. The output resets when the system is 
disarmed.  
0,9 
Kiss-Off after Exit Time 
This output operates after the first successful 
transmission to the base station receiver when Exit 
Time expires. The output resets when the system is 
disarmed. 
0,11 Entry 
Warning 
This output operates when during Entry Timer 1, 
Entry Timer 2, or Entry Guard Timer for STAY 
Mode. The output resets when the Entry Time 
expires.  
0,12  
Entry Warning + Day Alarm Resetting 
This output combines Entry Warning and Day Alarm 
Resetting so that either of these two events activates 
the output.   
If the output is activated by Entry Timer 1, Entry 
Timer 2, or Entry Guard Timer for STAY Mode, the 
output resets when the Entry Time expires or the 
system is disarmed.  
If a zone programmed for Day Alarm is activated 
when the system is disarmed, the output resets when 
the zone is resealed. You can turn Day Alarm on and 
off by pressing and holding [4]. Refer to Section 14.1 
Day Alarm Information
 on page 53 for programming 
zones to operate for Day Alarm. 
0,13 
Exit Warning + Entry Warning + Day Alarm 
Resetting 
This output operates when the system is armed, 
regardless of whether zones are sealed or unsealed, 
until Exit Time expires. 
The output operates again during Entry Time and 
resets when Entry Time expires or the system is 
disarmed.