D9112B | Program Entry Guide | 2.0  Area Wide Parameters 
EN | 26 
 
 
Bosch Security Systems | 2/04 | 74-06145-000-D 
 
A# Delay Res 
Default: 
No 
Selection: 
Yes or No 
Yes 
Restoral
 report is delayed until the 
area bell time expires, and the point 
returns to normal. 
No 
Restoral
 reports are sent when point 
restores, regardless of bell time. 
A# Exit Tone 
Default: 
Yes 
Selection: 
Yes or No 
Sound an exit tone during exit delay at command 
centers assigned to this area. 
A# Exit Dly Time 
Default: 
60 
Selection: 
0 to 600 
Exit delay time for this area. Select an entry that is a 
five sec. increment. 
Points programmed for “instant” alarms generate 
alarms immediately. Even during exit delay. 
Note: 
Fail to Close reports require exit delay time: If Fail 
To Close in Opening and Closing is programmed 
YES, you must enter an exit delay time. 
A# Auto Watch 
Default: 
No 
Selection: 
Yes or No 
Yes 
When disarmed, this area automatically goes into watch mode regardless of the status of Watch 
Mode before the area is armed. 
Automatic Watch does not affect manual Watch Mode toggle. You can still control Watch Mode 
using Command 6. 
No 
Watch Mode status is maintained between arm/disarm cycles. If the Watch Mode was ON at the 
time the area was armed, it will be ON again when the area is disarmed. If the Watch Mode was 
OFF at the time the area is disarmed, it will be OFF when the area is disarmed. 
Note: 
Watch Mode does not work while the area is perimeter armed. 
A# Verify Time 
Default: 
60 
Selection: 
10 to 60 sec. 
Alarm Verification is designed for use with smoke 
detectors to reduce the number of false fire alarms. 
When 
Verify Time
 is programmed, the panel can 
double check smoke detector point activations 
before generating alarm signals. 
Note: 
Check with your Authority Having Jurisdiction (AHJ) 
to determine the maximum verification time allowed. 
Points are programmed individually to activate the 
verification feature. See Point Index. Any resettable 
fire point can activate alarm verification for the area 
to which it is assigned. Bosch Security Systems 
recommends the use of separate area alarm-
verification relays. 
To enable alarm verification on a point, program 
Point Index 
Fire Point
Alarm Verify
 , and 
Resettable
 as 
Yes. 
When an alarm verification point trips, the D9112 
automatically removes power to all resettable points 
connected to the areas 
Reset Sensors
 relay. The 
sensor reset removes power to the sensors for the 
amount of time programmed in 
Verify Time
. When 
power is reapplied, a 60 sec. confirmation window 
begins. If the detector is still in alarm, or trips again 
during the confirmation window, or if a different 
resettable verification point in the area trips, an 
alarm is generated. 
Example 1:  
Verify Time
 is set for 20 seconds. The alarm 
verification cycle starts when the detector trips. No 
report is generated.