D9112B | Program Entry Guide | 3.0  User Interface 
EN | 54 
 
 
Bosch Security Systems | 2/04 | 74-06145-000-D 
 
View Pt Status 
Default: 
Selection: 
Blank, E, or P 
View Point Status: View points assigned to the area 
where the command center is assigned. This function 
shows point text and the electrical condition 
(normal, open, short) of each point in the area. 
0101
0101
0101
 
 
Points 72 and 136 appear in the Point Status 
List. Notice that text for Commands 7 and 9 
is followed by a MISSING condition on point 
72 and point 136. Points 72 and 136 serve 
dual purposes. They are used for Command 
7 and Command 9, and they are also used to 
supervise the data expansion bus. When you 
see that points 72 and 136 are missing, do 
not be alarmed. When these points are 
missing the point bus is normal. 
See Command Center Function Selections in the 
introduction to the Command Center Functions 
programming module for descriptions of selections. 
L## View Pt Stat 
Default: 
See 
Program Record Sheet
 
Selection: 
Blank or E 
View Point Status: See Authority Level Selections in 
the introduction to the Authority Lvl Assign 
programming module for descriptions of selections. 
Walk Test 
Default: 
Selection: 
Blank, E, or P 
Walk Test [COMMAND] [4] [4]: 
Test controlled points in disarmed areas within the 
Scope
 of the command center without sending 
reports to the central station. 
See Command Center Function Selections in the 
introduction to the Command Center Functions 
programming module for descriptions of selections. 
L## Walk Test 
Default: 
See 
Program Record Sheet
 
Selection: 
Blank or E 
Walk Test: See Authority Level Selections in the 
introduction to the Authority Lvl Assign programming 
module for descriptions of selections. 
Fire Test 
Default: 
Selection: 
Blank, E, or P 
Fire Test [COMMAND] [5] [8]: 
Test 24-Hour points in areas within the 
Scope
 of the 
command center where the function is entered. 
When a Fire Test is initiated one person can 
typically test a fire system without assistance. The 
following features are provided with the Fire Test 
Mode: 
• 
Central station report is transmitted when the 
Fire Test Mode is initiated and when it is 
terminated. 
• 
Local alarm annunciation without report 
transmission. 
 
All reports from 24-Hour points within the 
Scope of the command center are 
suppressed during Fire Test. 
• 
Automatic smoke detector reset (executing Reset 
Sensors from the Function Menu is not required 
after each device is tested). 
• 
Command centers equipped with an alpha-
numeric display show a sequential count after 
each point is activated and restored. 
• 
Printed record of each alarm test response is 
available if a local printer is installed and has the 
Scope 
required to record events from the area 
being tested (D9131 Printer Interface required). 
See Command Center Function Selections in the 
introduction to the Command Center Functions 
programming module for descriptions of selections. 
L## Fire Test 
Default: 
See 
Program Record Sheet
 
Selection: 
Blank or E 
Fire Test: See Authority Level Selections in the 
introduction to the Authority Lvl Assign programming 
module for descriptions of selections.