Bosch Appliances Home Security System D9112B User Manual

Page of 96
D9112B | Program Entry Guide | 10.0  Skeds 
EN | 86 
 
 
Bosch Security Systems | 2/04 | 74-06145-000-D 
 
Log % Full 
Default: 
Blank 
Selection: 
Blank, 1 to 128, A, B, or C 
Enter the number of the relay that activates when 
the log has reached the programmed percentage of 
its capacity as programmed in RAM Parameters 
program item 
Log % Full
. This relay provides a 
steady output until a “vacuum log” is performed 
from the RAM, or the panel is reset. 
Summary Fire 
Default: 
Blank 
Selection: 
Blank, 1 to 128, A, B, or C 
Enter the number of the relay that activates when a 
fire point goes into alarm. This relay provides a 
steady output until the alarm is cleared from alarm 
memory at the command center. 
Summary Alarm 
Default: 
Blank 
Selection: 
Blank, 1 to 128, A, B, or C 
Enter the number of the relay that activates when a 
controlled point goes into alarm. This relay provides 
a steady output until the alarm is cleared from alarm 
memory at the command center. 
Summary Fire Tbl 
Default: 
Blank 
Selection: 
Blank, 1 to 128, A, B, or C 
Activates when any fire point in the panel is in 
trouble. This relay provides a steady output until the 
trouble is cleared from alarm memory at the 
command center. 
Summary Trouble 
Default: 
Blank 
Selection: 
Blank, 1 to 128, A, B, or C 
Activates when any on-fire point in the panel is in 
trouble. This relay provides a steady output until the 
trouble is cleared from alarm memory at the 
command center. 
10.0 Skeds 
Use the Skeds module to program the D9112 to 
automatically execute functions on a specific date or 
day of the week. You can program up to seventeen 
Skeds in the D9112. 
Each Sked can be programmed with one of fifteen 
functions. Some functions codes require that you 
enter additional parameters. The functions and their 
associated parameters are listed in the “Sked 
Function Code Table” in the Program Record Sheet
and they are explained in detail following the 
S## 
Function Code 
prompt. 
Each Sked can be programmed with up to four 
Holiday Indexes. The Holiday Indexes can be used 
to execute the Sked on the holidays in the addition 
to the Date or Day(s) of the week, or they can be 
used to prevent the Sked from executing on the 
holidays (see 
S## Xept Holiday
). 
Sked Number 
Default: 
Selection: 
1 to 17 
Enter the number of the Sked you are programming.