D9412GV2/D7412GV2 | Operation and Installation Guide | 4.0  Installation 
 
16 
Bosch Security Systems, Inc. | 5/05 | F01U003641B 
 
4.4 
Installing the Control Panel 
1.  Place the control panel over the inside back of the 
enclosure, aligning the large rectangular openings 
of the mounting skirt with the mounting hooks of 
the enclosure. Slide the control panel down so that 
it hangs on the hooks. Refer to Figure 2, Item 2 on 
page 15.  
2.  Remove the tape from the #6 x 1/4-in. screw in 
the mounting tab on the control panel. The screw 
passes through the mounting tab and into the skirt 
mounting hole in the enclosure. Tighten the screw 
to secure the control panel in the enclosure. 
3.  Connect earth ground to the control panel before 
making any other connections. Refer to Section 4.5 
Connecting Earth Ground
4.5 
Connecting Earth Ground 
4.5.1 Terminal 
10 
To help prevent damage from electrostatic charges or 
other transient electrical surges, connect the system to 
earth ground at Terminal 10 before making other 
connections. Recommended earth ground references 
are a grounding rod or a cold water pipe. 
 
Warning: 
Do not use telephone or electrical ground 
for the earth ground connection. Use  
1.8 mm (14 AWG) to 1.5 mm (16 AWG) 
wire when making the connection.  
Do not connect other control panel 
terminals to earth ground. 
4.5.2 
Ground Fault Detect Enable 
 
A ground fault is a circuit impedance to earth 
ground. The control panel has a ground fault 
detection circuit that, when enabled, detects 
ground faults on Terminals 1 to 9 and 11 to 32. 
The control panel also detects and annunciates 
ground faults on any device connected to it.  
 
To enable ground fault detection, the Ground Fault 
Detect Enable jumper (S4) (Figure 3) must be 
locked (closed) and a non-zero value must be 
entered in the Area 5 Silent Alarm Relay. When 
jumper S4 is in the unlocked (open) position, the 
control panel does not detect ground fault 
conditions.  
 
If a ground fault condition occurs, the keypads 
display 
SERVC GND FAULT
 and the control panel 
transmits a 
GROUND FAULT TROUBLE, AREA 1
 
(Modem IIIa
2
 format only).  
When the control panel recognizes that the ground 
fault condition is corrected, and remains corrected 
for between 5 to 45 consecutive seconds, a Restoral 
Report is sent. 
 
 
The D9412GV2 and D7412GV2 Control 
Panels log and print a Ground Fault event 
as a Trouble Point 256 if communicating in 
Modem IIIa
2
 format. If communicating in 
BFSK format, the control panels generate 
an Alarm Zone 5 event. 
 
Figure 3: 
Ground Fault Detection 
GROUND FAULT DETECT
Enabled
Disabled
S4
PHONE
LED
RED
ON when
communicating
OFF when idle
PHONE LINE SEIZED
TIP
RING
TELCO CORD
MODEL D161
3
1
2
 
1 -  With S4 closed, control panel detects ground 
faults. 
2 -  With S4 open, control panel does not detect 
ground faults. 
3 -  S4, Ground fault detect enable.