D9412GV2/D7412GV2 | Operation and Installation Guide | 9.0   Off-Board Points 
 
34 
Bosch Security Systems, Inc. | 5/05 | F01U003641B 
 
9.0   Off-Board Points 
9.1 
Point (Zonex) Bus: D9412GV2 Terminals and D7412GV2 Terminals  
9.1.1 POPIT 
Modules 
The D9412GV2 can use point of protection input transponder (POPIT) modules to provide a maximum of 238 
off-board points, bringing the total number of points the D9412GV2 can monitor to 246. The D7412GV2 
provides up to 67 off-board points, bringing the total number of points the D7412GV2 monitors to 75. Each off-
board point requires a POPIT Module.  
9.1.2 POPEX 
Modules 
POPITs connect to supervised two-wire data expansion loops run from POPIT to POPIT throughout the 
premises. Data expansion loops connect to a D8125 Point of Protection Expander (POPEX) Module. POPEX 
Modules have power and data connections to the point bus on the control panel (Table 11). 
Table 11: 
POPEX Modules 
 
Model Power 
Data 
D9412G 
Terminals 23 and 24 
Terminals 25 and 26    
or 
Terminals 27 and 28 
D7412G 
Terminals 3 and 9 
Terminals 22 and 28 
9.1.3 Missing 
Conditions 
If a programmed POPIT is disconnected from the expansion loop, a missing condition appears immediately and 
the event is logged. The missing condition might also be sent to a central station or printed to an on-site printer, if 
programmed to do so. Refer to the D9412GV2/D7412GV2 Program Entry Guide (P/N: F01U003636) for 
programming options.  
9.1.4 
Extra Point Events 
Extra Point events are generated when a POPIT connected to the data expansion bus does not have an assigned 
Point Index. Table 12 shows when an Extra Point event is or is not generated. Table 13 on page 35 shows 
additional error conditions that can occur for the off-board points. 
Table 12: 
Extra Point Events 
 
A POPIT connected to the data 
expansion bus does not have an 
assigned Point Index and: 
Extra Point event? 
Additional Information 
Data expansion bus is disconnected 
No 
Keypad does not annunciate or display a trouble condition. 
Data expansion bus restores to normal 
condition after an open condition 
Yes 
 
Keypad annunciates and displays a trouble condition 
 
Extra Point is logged and might be programmed to 
send reports to the central station or to an on-site 
printer. 
Point input changes status from normal 
to open or shorted 
No 
Keypad does not annunciate or display a trouble condition. 
During a Service Walk Test, the point 
input changes status from normal to 
open or shorted 
Yes
 
 
Keypad annunciates and displays a trouble condition 
 
Extra Point is logged and might be programmed to 
send reports to the central station or to an on-site 
printer. 
 
 
The Service Walk Test never shows the electrical state of a point as “Extra.”