10.2.2 Installation 
Install the D811 in the enclosure with the control panel 
(Figure 22) or in an adjacent enclosure no more than  
1.5 m (5 ft.) from the control panel. Use 1.5 mm  
(16 AWG) to 0.8 mm (22 AWG) wire.  
To install D811 Modules in the enclosure with the 
control panel: 
1.  Align the D811 Module with any of the four 
mounting locations in the enclosure (Figure 2 on 
page 15). 
2.  Using the screws provided with the module, secure 
it in the enclosure. 
 
Use the D137 Mounting Bracket or D9002 
Mounting Skirt to install D811 Modules in 
enclosures with no available module mounting 
locations.  
10.2.3 Wiring 
Connections 
Power down the control panel to connect D811 
Modules as shown in Figure 22 on this page and 
Figure 23 on page 52.  
 
 
The D811 for Relay 53 connects to 
Zonex 1. 
The D811 for Relay 117 connects to 
Zonex 2 on the D9412GV2. 
 
Figure 22:  D811 Module Wiring to the D9412GV2 
Reset Pin
Disable All Except Battery
Charging And Programming
PERIPHERAL DEVICE CONNECTIONS
RED
POWER +
YELLOW
DATA BUS A
GREEN
DATA BUS B
BLACK
COMMON
ZONEX OUT 1
ZONEX IN 1
N.F.P.A.
Style 3.5
Signaling
Line
Circuits
32
31
30
29
28
27
ZONEX OUT 2
26
25
ZONEX IN 2
ZONEX POWER +
24
ZONEX COMMON
23
21
22
5
GND
AUX
DATA
5
GND
AUX
DATA
3
2
1
GRN
D5200/D5360
PROG CONN
Point 8
S3 Option
Closed = 1K
Ω
 EOL
Normal Operation
Open =AB-12 UL
Bell Box 220 K
Ω
 
1 -  D811 for Relay 53 
2- 
D811 for Relay 117 
3- On-board 
points