D9412GV2/D7412GV2 | Operation and Installation Guide | 11.0  Arming Devices 
 
54 
Bosch Security Systems, Inc. | 5/05 | F01U003641B 
 
You can connect devices to the data bus (Terminals 30 
and 31) by parallel wire run from the control panel to 
each device, wire from device to device, or a 
combination of the two using a maximum of 4572 m 
(15000 ft) of 0.8 mm (22 AWG) wire for all devices 
connected to the SDI Bus combined.  
Wire Limits for Individual Keypads 
 
Limit most keypads to 610 m (2000 ft) per run. 
 
Limit D9210B Modules to 457 m (1500 ft) per run 
(762 m [2,500 ft] if using an external power 
supply). 
 
Limit D9131A Modules to 305 m (1000 ft) per run. 
Extra Power for More Keypads 
The D1255 Command Center draws 104 mA when 
idle. It draws 206 mA with the keys lit and the sounder 
activated. Review Section 6.0 Power Outputs on page 25 
to determine the total power output requirements for 
the system.  
One or more D8132 Battery Charger/Power Supply 
Modules can be added for the number of keypads 
used. Figure 24 shows the D8132 powering keypads in a 
stand-alone configuration. 
For UL Certificated accounts, use a UL Listed auxiliary 
12 VDC or 24 VDC regulated, power-limited power 
supply for Fire Protective Signaling Units and 
Commercial or Residential Burglar Units. The D8132 
is not UL Listed as a stand-alone power supply. 
 
 
The control panel and the D8132 (or 
other power supply) must share 
COMMON. 
Figure 24 shows the common form of the 
D8132 Module connected to the common 
on the keypad and the common on the 
control panel. Any stand-alone power 
supply, powering any device connected to 
the control panel, must also be connected 
to a common terminal on the control panel. 
If using the ground fault detection capability 
on the D9412GV2 and D7412GV2 
Control Panels with an external power 
supply, ensure that the external selected 
power supply isolates its earth ground 
connection from the negative side of the 
auxiliary power output. External power 
supplies that do not isolate earth ground 
can cause ground fault conditions on the 
control panel. 
 
 
 
Figure 24:  Power at Keypads 
1
2
2
3
3
4
4
5
 
1 -  To control panel 
2 -  +12 VDC 
3 -  Data 
4 -  Common 
5 -  D8132 or external power supply