Bosch Appliances Home Security System D9412GV2 User Manual

Page of 74
D9412GV2/D7412GV2 | Operation and Installation Guide | 3.0  Overview 
 
Bosch Security Systems, Inc. | 5/05 | F01U003641B 
 
3.0 Overview 
3.1 
Configuration and Parts 
Figure 1: 
System Configuration 
Use keypads or keyswitches to arm the control
panel by area. Each control panel can have up to eight
areas. Each area can have its own account number or
areas can be grouped together with a common account
number. Points of protection are assigned to areas.
Control
Panel
On-Board Points
1 to 8
D9131A Module connects
to a parallel printer to print
the event log.
D928 Module allows the control
panel to monitor two phone lines.
Each D8128D OctoPOPIT combines
eight POPIT points in one module.
D8132 Modules (two 12 VDC, 7Ah batteries)
provide additional power for keypads and
other powered devices.
D8129 OctoRelay provides alarm
and auxiliary relay output.
(Other functions available.)
D9210B Modules can be
used for access control.
DX4020 allows communciation
over a Local or Wide Area Network
(LAN/WAN).
D8125, D8125INV, or
D8125MUX Interface
used for point expansion.
 
 
Table 2: 
GV2 Series Control Panel Differences 
 
Features 
D9412GV2 
D7412GV2 
D7212GV2 
Access Control 
Yes - 8 doors 
Yes - 2 doors 
No 
Arm/Disarm Passcodes 
249 
99 
99 
Cards/Tokens 
996 
396 
N/A 
Passcode-Protected 
Custom Functions 
16 
Number of Printers 
Number of Points 
246 
75 
40 
Number of Relays 
128 
64 
24 
Number of Areas