D7212G Operation and Installation Guide
Page 36
© 2003 Bosch Security Systems
4998138544C
D7212G
On-board Points
7.5
Wiring Information for Installations using the Ademco AB-12 Bell/Housing
1 2 3 4 5 6
Bell
B
e
l
l
T
a
m
p
e
r
s
Outer
Bell Box
Inner Bell
Box Lining
EOL
220 k
Ω
½ W
EARTH GROUND
COMMON
BATTERY NEGATIVE ONLY
Maximum Charging
Current 1.4 Amps.
BATTERY POSITIVE ONLY
RELAY A
RELAY B
RELAY C
+ AUX POWER
CLASS 2 TRANSFORMER
16.5 VAC 40 VA 60 Hz
Model D1640
Internally Fused - Do Not short
Requires Unswitched Outlet
Do Not Share With Other Equipment
PROGRAMMABLE
ALARM OUTPUTS
Terminals
Requires Optional
Model D136 Relay
In ALT ALARM
& SW AUX
&
7
8
GROUND FAULT DETECT
Enabled
Disabled
PHONE
LED
RED
ON WHEN
COMMUNICATING
OFF WHEN IDLE
Digital Alarm Communicator Transmitter
Reference D7212G Approved Applications Compliance Guide (P/N:4998138560___)
For System Wiring Diagram, Issue A
Reference D9000/D9000G Series Technogram (P/N:33284___)
For Compatible Smoke Detectors
POWER SUPPLY REQUIREMENTS
The Power Supply Provides a Maximum of 1.4 Amps For The Control
Panel and All Accessory Devices. For System Loading, See D7212G Operation
and Installation Guide (P/N:4998138544___).
All External Connections Except Terminal   5   (Battery Positive) Are Inherently Power
Limited. Requirements For Battery Standby Time May Reduce Allowable Output.
CAUTION: 
See D7212G Operation and Installation Guide (P/N:4998138544)
For Power Requirements Relating to Terminals   6      7
WARNING!
Multi-Battery Installation Requires
Model D122 Dual Battery Harness.
Improper Installation Can Be a Fire
Hazard.
Battery: Replace Every 3 to
5 years with Model D126, 12 V
7 Amp Hr Lead Acid Battery
D7212G Control/Communicator is UL Listed For Household
Fire Alarm, and Central Station, Local, Police Station Connect and Household Burglar Alarm.
System is Intended To Be Checked By A Qualified Technician At Least Every 3 Years.
The types of initiating circuits the panel has been approved for are A, M, W, SS.
VOLTAGE RANGES
Open
3.7 - 5.0 VDC
Normal
2.0 - 3.0 VDC
Short
0.0 - 1.3 VDC
GRN
Reset Pin
Disable All Except Battery
Charging And Programming
PERIPHERAL DEVICE CONNECTIONS
RED
POWER +
YELLOW
DATA BUS A
GREEN
DATA BUS B
BLACK
COMMON
ZONEX OUT 1
ZONEX IN 1
N.F.P.A.
Style 3.5
Signaling
Line
Circuits
PROG
CONN
4998138540B
LOOP START
GND START
GROUND START
Point 8
GND FAULT
Detect
E
N
A
B
L
E
D
I
S
A
B
L
E
12
11
13
Point 1 Point 2
15
14
16
Point 3 Point 4
18
17
19
Point 5 Point 6
21
20
22
Point 7 Point 8
GROUND START
Requires Relay
Model D136 in
Ground
Start Socket
LEDs Off When Normal
Charging Status
Low Battery - 12.1 VDC
YEL
RED
10.2 VDC - Battery Load Shed
This equipment should be installed in accordance with the NFPA 70 (National Electrical Code)
and NFPA 72 (National Fire Alarm Code) Household Fire Warning Systems and under the limits of the
Local Authority Having Jurisdiction (National Fire Protection Association, Batterymarch Park, Quincy,
MA 02269) Printed information describing proper installation, operation, testing, maintenance,
evacuation planning and repair service is to be provided with this equipment.
D7212G
Figure 12: Wiring for Installations using the Ademco AB-12 Bell/Housing
1.
Disconnect the wire jumper from Terminal 4 to the inner housing of the Bell Box (prevents a ground fault
condition).
2.
Connect wiring between the control and Bell Box as shown above. To use the AB-12 Bell/Housing, place the S3
switch in the disabled (open) position. The EOL used in the AB-12 Bell/Housing must be a 220 k
Ω
, 0.5 
Ω
resistor.
3.
Program Point 8 as 24-hour, ALARM on open and short. (PT TYPE 0, PT RESPONSE 0).