en | 236
Normally, the call station interface and the remote call 
station are powered from the network. To make sure 
that they receive power when the network is not 
available, external power supplies can be connected to 
the call station interface and the remote call station. See 
section 22.3.3 for more information.
20.3.5 Connecting control inputs
The remote call station has 2 control inputs (refer to 
figure 20.5 and table 20.1). The control inputs can 
receive signals from third party equipment that must 
trigger actions in the Praesideo system. The control 
inputs can be configured to act on contact make or on 
contact break (see section 43.4.4). The maximum length 
of the connected cables is 3 meter.
It is also possible to supervise the cables for 
short-circuits and open connections (see figure 20.6 and 
figure 20.7). 
Whether a control input is actually 
supervised or not is defined in the configuration.
Warning
For safety reasons, you must use a current 
limited external power supply complying with the 
60065 standard for audio/video usage or 
equivalent, with a maximum output current of 5A, 
or you must use an external fuse (5 A max, slow) 
in the wiring of the Kycon KPP-4P connector. 
For application in emergency sound systems in 
Europe, the installer must use a power supply 
with EN54-4 certification.
Caution
For USA: only use a power supply of the type 
Mean Well PLN-30-24, PLN-30-36, PLN-30-48, 
PLN-60-24, PLN-60-36, PLN-60-48, 
PLN-100-24, PLN-100-36 or PLN-100-48.
For CANADA: only use a power supply of the type 
Mean Well PLN-30-24, PLN-30-36, PLN-60-24, 
PLN-60-36, PLN-100-24 or PLN-100-36.
Other types of power supply are not tested with
Praesideo and may cause harm.
figure 20.6: Supervised control input
figure 20.7: Non-supervised control input
Warning
Do not connect DC or AC signals to the control 
inputs, otherwise the input circuit may be 
damaged. Only use voltage-free contacts.
10k
Ω
10k
Ω
GND
Control input
GND
Control input