Bosch Appliances Home Security System 3.5 User Manual

Page of 498
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | 9 | System Configuration
en | 365
table 43.17: Audio outputs configuration
Item
Value
Description
Output n
Unique name for the audio output. The output can be 
enabled and disabled using the check box.
Pilot tone
On, Off
Switches the pilot tone for loudspeaker monitoring on 
(On) and off (Off). This pilot tone is used to monitor the 
connected basic amplifier and the secondary side of its 
transformer for short-circuits. It also supervises the 
amplifier for failures and is used by the line supervision set.
GND supervision
On, Off
Switches ground supervision of the loudspeaker line on 
(On) and off (Off).
Mains power 
supervision
On, Off
Specifies whether the mains power of the connected 
basic amplifier must be supervised. When Mains power 
supervision is On and the mains power is failing, a fault 
event is generated. Setting Mains Power Supervision to 
Off when mains power is used, results in a system that 
does not detect mains power failures.
Back-up power 
supervision
On, Off
Specifies whether the back-up power of the connected 
basic amplifier must be supervised. When Back-up power 
supervision is On and the back-up power is failing, a fault 
event is generated. Setting Back-up power supervision to 
Off when back-up power is used, results in a system that 
does not detect back-up power failures. 
Lsp connection
Output A and B in same 
area (redundant).
Output A and B in 
separate areas (Not 
redundant).
Class-A loop from 
output A to B.
The outputs A and B each have loudspeakers that cover 
the same area. Both outputs A and B are normally active. If 
a line fault occurs on either output A or B, that output will 
be switched off.
The outputs A and B each have loudspeakers that cover 
different areas and are not close together. Both outputs A 
and B are normally active. If a line fault occurs on either 
output A or B, that output remains active. Only in case of 
an overload or short circuit on either output A or B, that 
output will be switched off. 
The outputs A and B have connections to the same 
loudspeakers. Output A is normally active, output B is 
normally off. If a line fault occurs detected by a supervision 
board, output B becomes active too.
Line/Lsp supervision
On, Off
Sets the line / loudspeaker supervision for group A or 
group B.
Configure supervision 
devices A
Opens a screen to configure LBB4441 and LBB4443 
supervision devices (see section 43.3.5) on group A.
Configure supervision 
devices B
Opens a screen to configure LBB4441 and LBB4443 
supervision devices (see section 43.3.5) on group B.