Bosch 2000 User Manual

Page of 72
2000 Series | Program Entry Guide | 8.0 
Bell 
EN | 29 
 
Bosch Security Systems | 7/05 | 35114F 
 
8.0 Bell 
The prompts in this group configure the Alarm Output 
(bell) at Terminals 4 and 5. 
1 Bell Time 
 
 
Default: 
Selection:  0 to 255
 
The 
Bell Time
 prompt sets the minutes of alarm 
output at terminals 4 and 5. Both Fire Bell function 
(pulsed output) and the Burglary Bell function (steady 
output) follow the 
Bell Time
 duration. 
Enter the number of minutes of alarm output at 
Terminals 4 and 5 for both Fire and Burglary (Non-
Fire) functions. If you are using the 
Alarm on 2 Fail
 
feature, program at least 3 minutes in 
Bell Time
Refer to below. 
 
 
Check with your Authority Having 
Jurisdiction (AHJ) to determine the 
appropriate Bell Time for your installation. 
Many communities restrict bell time. 
2 Bell Time 
 
 
Default: 
No
 
Selection:  Yes, No
 
0 No
 
1 Yes 
If you set the 
Bell Test
 prompt to Yes, the system 
sounds the bell for 2 seconds when users turn the 
system All On by pressing the [9] key. 
If the system sends Closing Reports, the bell sounds 
when the receiver acknowledges the Closing Report. If 
the system does not send Closing Reports, the bell 
sounds at the expiration of Exit Delay. 
3 Single Ring 
Default: 
No
 
Selection:  Yes, No
 
0 No
 
1 Yes 
Set the 
Single Ring
 prompt to Yes to limit the alarm 
output from the same Non-Fire point to one per 
arming cycle. Setting this prompt to No allows every 
alarm activation from a Non-Fire point to generate an 
alarm output during an arming cycle. 
Fire points always provide alarm output for every 
alarm activation. 
Single Ring
 only affects the 
alarm output. It does not prevent reports from 
being sent. 
4 Alarm on 2 Fail 
Default: 
No
 
Selection:  Yes, No
 
0 No
 
1 Yes 
Setting the 
Alarm on 2 Fail
 prompt to Yes 
provides an alarm output after two failed attempts 
to transmit an Alarm Report from any point when 
the system is on. Alarm output is provided even if 
the point is not programmed for alarm output. 
Bell Time
 must be programmed with at least 3 
minutes to use the 
Alarm on 2 Fail 
feature. 
Set this prompt to No if you want to prevent an 
alarm output from Silent points even when the 
system fails to communicate with the receiver. 
Refer to Section 11.0 Point Codes for information on 
programming points for alarm output.