Bosch 2000 User Manual

Page of 72
2000 Series | Program Entry Guide | 11.0 
Point Codes 
EN | 40 
 
Bosch Security Systems | 7/05 | 35114F 
 
 
Table 5: continued 
 
Display Selection 
Description 
Controlled, Part, No 
Delay 
When control panel is All or Part On (armed), short or open causes alarm 
response.  
Part points must be normal (not faulted) or bypassed before control panel 
can be Part armed. 
If an alarm occurs on these points within 2 minutes of a closing (exit time 
expired, Excursion/Exit included), the system sends a RECENT CLOSING 
message with the Alarm Report. 
If these points are faulted at the end of exit delay, the system waits a period 
equal to entry delay before sending an Alarm Report. If the system is not 
turned off, it sends an EXIT ERROR message with the Alarm Report. 
Missing Controlled points generate an alarm response when on, a trouble 
response when off. 
RF Tamper for a Controlled point generates an alarm response when on, a 
trouble response when off. 
Keyswitch 
Shorting then restoring Keyswitch points toggles the control panel from All 
(or Part) On to off, off to All On. 
The trouble option (refer to Section 11.3 Digit 3, Point Options)determines 
how Keyswitch points respond to opens when the system is off. When the 
system is All or Part On, an open produces an alarm response. A keyswitch 
always causes a trouble condition if it is opened in the off state, regardless 
of the value programmed in Digit 3. 
If an alarm occurs on these points within 2 minutes of a closing (exit time 
expired, Excursion/Exit included), the system sends a RECENT CLOSING 
message with the Alarm Report. 
Missing Keyswitch points generate an alarm response when on, a trouble 
response when off. 
RF Tamper for Keyswitch points generates an alarm response when on, a 
trouble response when off.