Relays 
EN | 55 
 
Bosch Security Systems | 7/05 | 35114F 
 
 
Table 18: continued 
 
Programmers Keypad 
Description 
A,B,C Key, 
Momentary 
Activates the relay output when a user presses a selected function key. The relay 
output activates for 10 seconds. Do not program both relays for this function, 
doing so might cause inconsistent relay operation. 
Select the function keys to monitor at the Parameter prompt. 
Off with Passcode 
Activates the relay for 10 seconds when a selected user turns the system off with 
a passcode.  
Note: 
Do not program both relays for this function, doing so can cause inconsistent relay 
operation.  
Select the Users to monitor at the Parameter prompt. 
Follow Alarm Output 
10 
Parallels activity at the alarm output (Terminals 4 and 5). 
All On 
11 
Activates the relay at the start of exit delay when the system is All On. The 
output remains activated until the system is turned off.  
Part On 
12 
Activates the relay at the start of exit delay when the system is Part On. The 
output remains activated until the system is turned off.  
Reset  
13 
Activates the relay output when a user presses the [3] key to reset the system. 
The relay output activates for 4 seconds. Do not program both relays for this 
function, doing so might cause inconsistent relay operation. 
AC Failure 
14 
Provides a steady output when the system detects a loss of power at Terminals 1 
and 2. The driver remains activated until AC power restores. 
Battery Trouble 
15 
Provides a steady output when the system detects a low or missing battery 
condition. The relay remains activated until the battery restores. 
Communication Fail 
16 
Provides a steady output when the system fails to communicate with the receiver 
within ten dialing attempts when two phone numbers are programmed, or five 
dialing attempts when one phone number is programmed. The relay remains 
activated until the system successfully communicates a report to the receiver. 
Communicating 
17 
Activates the relay output when the system seizes the phone line. The relay 
remains activated until the system releases the phone line. 
Ground Start 
18 
Activates the relay output for 900 milliseconds after the system seizes the phone 
line. Use this function to generate dial tone on ground start systems.  
Note: 
Do not program both relays for this function, doing so can cause inconsistent relay 
operation. 
Entry and Exit Delay 
19 
Relay provides a steady output during entry and exit delays. 
Extended Delay 
20 
Relay provides a steady output during extended delay.  
The relay does not activate if you fault an Extended Delay point before you start 
exit delay, or if you bypass the Extended Delay point while you are in exit delay. 
Pulsed Output 
21 
This function provides a continuous pulsed output.  
Do not assign this function to a relay without “anding” it to another function. 
Refer to the Relay 1 Logic 1 and Relay 2 Logic 1 prompts in Section 13.1 Relay 
Function Logic
. For example, “anding” this function to the Alarm function results 
in pulsed output for the duration of Bell Time.  
The Pulsed Output does not activate when alarms from A, B, C Keys occur.