Sequence of Operation
Burner States
Standby: The burner is idle, waiting 
for a call for heat. 
Valve-On Delay: The igniter and 
motor are on while the control delays 
turning on the oil solenoid valve for 
the programmed time.
Trial For Ignition: The oil solenoid 
valve is energized.  A fl ame should be 
established within the factory set trial 
for ignition time (“lockout time”).
4. Lockout:  The control has shut 
down for one of the following safety 
reasons:
a.  The trial for ignition (lockout) 
time expired without fl ame being 
established.
b.  The cad cell detected fl ame at the 
end of the Valve On Delay state.
c.  The pre-set time allotment for 
relighting is exceeded.
d.  Failed welded relay check.
If the control detects a welded motor 
contact, the motor only will cycle 5 
1.
2.
3.
seconds on, 5 seconds off, 3 times 
before locking out. 
  To reset the control from lockout 
interrupt power for at least 2 seconds.
Ignition Carryover: Once fl ame is 
established, the igniter remains on for 
10 additional seconds to ensure fl ame 
stability.  
Run: The fl ame is sustained until the 
call for heat is satisfi ed.  The control 
then switches to Motor-Off Delay, 
if applicable, or it shuts down and 
returns to Standby.
Relight: If the fl ame is lost while 
the burner is fi ring, the control 
immediately repeats the ignition 
sequence.  The control will continue 
to Relight each time the fl ame is 
lost, until it reaches a pre-set time 
allotment.  The control will then 
go into Lockout instead of Relight.  
This feature prevents excessive 
accumulation of oil in the equipment’s 
combustion chamber.
Motor-Off Delay: If applicable, the oil 
solenoid valve is turned off and the 
control delays turning the motor off for 
the set motor-off delay time before the 
control returns to standby. Note that to 
utilize the motor off delay, power must 
remain to the red wire after the call for 
heat ends. (Enable input turned off, 
see Figure 2.)
5.
6.
7.
8.
2
1
3
5
6
8
4
7
Standby
Motor-off 
delay
Valve-on 
delay
Trial for
ignition
Ignition 
carryover
Run
Lockout
Relight