Bosch Appliances Video Game Controller D9412GV2 User Manual

Page of 158
D9412GV2/D7412GV2 | Program Entry Guide | 4.0  RADXPNTS 
EN | 104 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
4.4 
COMMAND 7 and COMMAND 9 
 
 
Two relays can activate when this point 
enters into alarm if the P## Rly Resp 
These entries assign point indexes, BFSK report 
code, BFSK relay that activates, and the text for the 
COMMAND 7 and COMMAND 9 keypad functions. 
Type for this point is programmed. 
 
Use these codes to activate relays on the 
D8129 OctoRelay (or C8137 Transmitter 
Interface). You can assign the same code 
to several points providing a summary 
zone alarm output. When the point enters 
into alarm, the relay activates. When the 
alarm is acknowledged and is no longer 
scrolling in the keypad display, the relay 
resets. 
CMD7 Point Index 
Default: 
31 
Selection:  Blank (00) to 31 
This entry selects one of the 31 P## Index codes that 
define how the control panel reacts when a 
COMMAND 7 is initiated. 
 
P### Point Text 
Default: 
Refer to the program record sheet 
Selection:  Up to sixteen alphanumeric 
characters 
Enter alphabetic characters (A to Z) in capital letters. 
Enter up to sixteen characters of text to describe the 
point. This point text is shown at keypads, if the point 
is programmed as visible, and sent to the D6500 or 
D6600 when transmitting in Modem IIIa
2
 format (if it is 
a reporting point). 
Include the point number in custom point text. This 
helps the user when viewing events, creating 
bypasses, and so on. It can also simplify 
troubleshooting. 
 
 
When a D1260 Keypad is installed on the 
system, the point text for Points 240 to 
247 can be used for Area Name Text for 
Areas 1 to 8, respectively. Refer to Table 
33
 
Table 33: Point Text for Points 240 to 247 
 
Point Text 
Corresponding Area Name Text 
Point 240 
Area 1 
Point 241 
Area 2 
Point 242 
Area 3 
Point 243 
Area 4 
Point 244 
Area 5 
Point 245 
Area 6 
Point 246 
Area 7 
Point 247 
Area 8 
 
 
The point index code used for 
COMMAND 7 must not be used for any 
other points on the system. 
 
 
If the point index for COMMAND 7 has 
Fire points programmed as Yes, this 
causes access control doors to unlock if 
 
Fire Unlock is also programmed as Yes. 
Refer to the D9210B Program Entry 
Guide
  
(P/N: 32207). 
 
CMD7 BFSK/Relay 
Default: 
Selection: 
0 to 9 
This entry selects one of the digits shown for reporting 
in BFSK or for activating relays 73 to 80 (on the 
D9412GV2) or relays 9 to 16 (for the D7412GV2) 
when COMMAND 7 is initiated (refer to the 
P### BFSK/Relay prompt on page 103).  
COMMAND 7 does not activate the 
Summary Fire Alarm relay. 
 
CMD7 Point Text 
Default: 
[COMMAND][7] 
Up to sixteen alphanumeric 
Selection: 
characters 
Enter alphabetic characters A to Z in capital letters 
Enter up to sixteen characters of text to describe the 
point. This point text appears at keypads (if the point 
is programmed as visible) and sent to the D6500 or 
D6600 when transmitting in Modem IIIa
2
 format (if it is 
a reporting point).